RackSwitch G8264 Installation
52
Chapter 2: Installing the RackSwitch G8264
BPP-00039-00 rev 2, January 2011
Installing or Replacing a Fan Module
The RackSwitch G8264 contains four hot-swap fan modules. All four fan modules are required for
normal operation.
The switch continues to operate when there is one failed fan module. If one module fails, the switch
sends an error message. If a second module fails, the switch sends an error message, writes a failure
log to flash memory, and shuts down.
Each fan module has a green LED that is visible from rear panel. The LED shows the status of the
fan module, as follows:
LED on: Fans are operational.
LED off: Switch unit has no power.
LED blinks: Fan speed has failed. Replace the fan module.
Removing a Fan Module
To remove a fan module, perform the following steps:
1.
Loosen the retainer screw.
2.
Grasp the extractor handle and gently pull the fan module from the slot.
Installing a Fan Module
To install a fan module, perform the following steps:
1.
Remove the fan module from the anti-static shielded bag.
2.
Slide the fan module into the card guides in the open slot and gently push it all the way into the slot,
so that it firmly engages with the connector (see
Figure 22
).
Each fan module has a mechanical guide key to prevent you from inserting the module incorrectly.
3.
Tighten the retaining screw on the fan module. Torque the screw to approximately 4 inch-pounds
(0.5 Nm).
Caution—
Replace the fan module within 5 minutes to avoid overheating the switch.