CT-600-2
No. Description
Param. page
on HMI
Default
value
Default
unit
100 PID TV suction pressure (D)
PID 2 - 1
0
s
101 PID TD suction pressure
PID 2 - 1
1
s
102 PID setpoint ramp limit suction pressure
PID 2 - 1
10.0
min/bar
103 PID deadband suction pressure
PID 2 - 1
0.0
bar
104 PID output high limit suction pressure
PID 2 - 1
100
%
105 PID output low limit suction pressure
PID 2 - 1
-100
%
106 PID inner window I-part suction pressure
PID 2 - 1
0.0
bar
107 PID outer window I-part suction pressure
PID 2 - 1
0.0
bar
108 PID KP cold brine (P)
PID 2 - 2
5.0
%/°C
109 PID TN cold brine (I)
PID 2 - 2
60
s
110 PID TV cold brine (D)
PID 2 - 2
0
s
111 PID TD cold brine
PID 2 - 2
1
s
112 PID setpoint ramp limit cold brine
PID 2 - 2
2.0
min/°C
113 PID deadband cold brine
PID 2 - 2
0.0
°C
114 PID output high limit cold brine
PID 2 - 2
100
%
115 PID output low limit cold brine
PID 2 - 2
-100
%
116 PID inner window I-part cold brine
PID 2 - 2
0
°C
117 PID outer window I-part cold brine
PID 2 - 2
0
°C
118 PID KP discharge pressure (P)
PID 2 - 3
20.0
%/bar
119 PID TN discharge pressure (I)
PID 2 - 3
30
s
120 PID TV discharge pressure (D)
PID 2 - 3
0
s
121 PID TD discharge pressure
PID 2 - 3
1
s
122 PID setpoint ramp limit discharge pressure
PID 2 - 3
10.0
min/bar
123 PID deadband discharge pressure
PID 2 - 3
0.0
bar
124 PID output high limit discharge pressure
PID 2 - 3
100
%
125 PID output low limit discharge pressure
PID 2 - 3
-100
%
126 PID inner window I-part discharge pressure
PID 2 - 3
0.0
bar
127 PID outer window I-part discharge pressure
PID 2 - 3
0.0
bar
128 PID KP hot water (P)
PID 2- 4
5.0
%/°C
129 PID TN hot water (I)
PID 2- 4
60
s
130 PID TV hot water (D)
PID 2- 4
0
s
131 PID TD hot water
PID 2- 4
1
s
132 PID setpoint ramp limit hot water
PID 2- 4
2.0
min/°C
133 PID deadband hot water
PID 2- 4
0.0
°C
134 PID output high limit hot water
PID 2- 4
100
%
135 PID output low limit hot water
PID 2- 4
-100
%