CT-600-2
7
4
Technical data
4.1
ACP LINK panel
The ACP LINK panel is to be mounted on a support on or close to the ACP unit
(see section 6.2). The panel is partly pre-wired by BITZER but must be finally
wired and connected on site by the customer (see section 7.1). See also section
13.1 and 13.2 for parameters settings.
Supplier
WEG
Reference No.
31816777
Description
BITZER ACP LINK panel
Dimensions
H = 400mm, W = 400mm, D = 210mm
Color
RAL 7035
Enclosure class
IP54
Approvals
UL/CSA/CE/IEC
Temp./humidity range
Min. / max temperature: 0 / 55°C
Min. / max humidity: 10 – 90% (non-condensing)
Max. vibration levels
According to EN/IEC 61131-2:
3.5 mm constant amplitude (f = 5…8.4 Hz)
9.8 mm/s
2
(f = 8.4…150 Hz)
Display
Schneider HM HMIG3U
PLC
Schneider TM251MESE
Emergency & power
switch
WEG BC01F
Breakers
Main: 230V/120 Vac, 13A,
PLC, HMI, M172: 24 Vdc, 6A
OAHC (oil sep.): 230/120 Vac, 10A
Eco system: 230/120 Vac 10A
Compressor 1, 2, 3: 230/120 Vac, 4A
Schneider panel breakers Multi 9, C60SP, 1Pol, C3A
Schneider panel breakers Multi 9, C60SP, 2Pol, C4A, C6A, C10A, C13A
I/O
Power supply, safety chain, start signal, communication to/from related modules
and plant.
Communication ports
2 x Modbus TCP/IP on PLC (for HMI, SCADA, Ethernet and Devices)
2 x Modbus TCP/IP on HMI (for PLC and Wifi access point)
1 x Modbus RTU (RS485)
Power supply
230 Vac / 120Vac, +10%/-15%, min. 16A
24 Vdc, +20%/-15%, min. 10A
Mounting
Four M8 threaded holes, one in each corner of the back of the enclosure, for
mounting on a frame or support. Center distance between holes: 355mm.