TWG 01 01/2011
page 18/39
Delay time:
for impulse-type activation (not used)
for continuous activation by AB 01
(0.06 sec delay)
(0.2 sec delay)
(10 sec delay)
(15 sec delay)
To set the connection type and the alarm delay time proceed as follows:
Step Key
Effect
Yellow
LED
1.
Program call
1x flashing
2.
Program selection:
“Entry of alarm type“
1x flashing
3.
Selection of program step confirmed
2x flashing
4.
Information entry about connection
type: “Normally closed“
1x flashing
5.
or
Information entry about alarm delay
time
1x flashing
6.
Programming terminated
lights up for 1.5 sec
6.3
Recording of voice message
The maximum total duration of the alarm messages transmitted by the TWG 01 via telephone is 32 sec. If
you want to record a shorter message, you can terminate recording with the
key. You can divide the
32 seconds to up to 4 individual messages.
During recording keep close to the built-in microphone.
Step Key
Effect
Yellow
LED
1.
Program call
1x flashing
2.
Program selection:
“Voice recording “
1x flashing
3.
Selection of program step confirmed
lights up for 1.5 sec
4.
e.g.
Selection (0, 1, 2, or 3) of a message
with 3 zone operation
1x flashing
5.
Selection of program step confirmed
lit
6.
Voice entry
Entry of voice message via microphone
lit
32 sec after start of
recording
7.
or
End of voice recording
off