AS-i/CANopen Gateway
Appendix: The First Commissioning of AS-i
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
sue da
te
27
.1
.2
0
0
3
98
Connect another slave with address 0
to the AS-i line and allocate the
address 2 to it.
Connect the slave to the AS-i line. The
addressing is the same as for the pre-
vious slave.
The addresses of all slaves detected are now displayed sequentially.
Change to the protected operating
mode and store the AS-i configuration.
Leave the configuration mode by
pressing the “mode” button for at least
five seconds until the “prj mode” LED
goes out.
The configuration of the AS-i master is now finished.
Now the hierarchically higher fieldbus system can be put into operation.
What to do ?