36
Electrical Installation (cont.)
Wiring the fan motor: 9 lead, dual voltage, wye motor configurations
The motor wiring configurations shown below are applicable to 9 lead dual voltage wye wound motors rated for 230/460VAC and
330/600VAC. Consult the motor nameplate and/or wiring placard for verification of required wiring connections. Motors with terminal
blocks require ring terminals and a 7 mm nut driver for termination. The diagrams below include L2 and L3 swap to yield proper motor
rotation.
Note: Swapping leads to reverse rotation is done only on the output side of the drive.
U1
T1
V1
T2
W1
T3
U5
T7
V5
T8
W5
T9
U2
T4
V2
T5
W2
T6
U1
T1
V1
T2
W1
T3
U5
T7
V5
T8
W5
T9
U2
T4
V2
T5
W2
T6
Low Voltage
200–240VAC, 50–60Hz
330–350VAC, 50–60Hz
High Voltage
400–480VAC, 50–60Hz
575–600VAC, 50–60Hz
Jumper bars are
provided with the
motor
BLUE
RED
BLACK
YELLOW
ORANGE
BROWN
GREEN W/ YELLOW
GREEN W/ YELLOW
VAC from VFD
VAC from VFD
High V
oltage
Low V
oltage