PIVOT™ 180
WWW.BIGASSFANS.COM ©2011 DELTA T CORP. ALL RIGHTS RESERVED
26
Wiring specifications (fan controller)
Acceptable unshielded cable types
•
Stranded THHN/THNW, rated for 600V & 158°F-194°F (75° to 90°C) in metallic conduit.
Acceptable shielded cable types
Location
Rating / Type
Description
Standard
(Option 1)
600V, 75ºC or 90ºC (167ºF or 194ºF)
RHH/RHW-2
•
Four tinned conductors with XLPE insulation
•
Foil shield and tinned copper drain wire with 85% braid
coverage
•
PVC Jacket
Belden 29501-29507 or equivalent
Standard
(Option 2)
Tray rated 600V, 75ºC or 90ºC (167ºF
or 194ºF) RHH/RHW-2
•
Three tinned copper conductors with XLPE insulation
•
5 mil single helical copper tape (25% overlap minimum) with
three bare copper grounds in contact with shield
•
PVC Jacket
Shawflex 2ACD/3ACD or equivalent
Class I & II
Division I & II
Tray rated 600V, 75ºC or 90ºC (167ºF
or 194ºF) RHH/RHW-2
•
Three bare copper conductors with XLPE insulation with
impervious corrugated continuously welded aluminum armor
•
Black sunlight resistant PVC jacket overall
•
Three copper grounds on #10 AWG and smaller
General specifications
Adhere to the following guidelines:
•
The drain conductor included with shielded cables must be connected to both the main fan unit and the PE/Ground terminal of the
Variable Frequency Drive.
•
MC Cable MAY NOT be used for controller output/motor leads!
•
Do not use solid core wiring of any size or insulation class for controller output/motor leads!
Maximum cable lengths
To prevent nuisance trips, the all Single Fan Systems. Distance between controller and fan should not exceed 400 ft (122 m).
Recommended wire size
•
A minimum of 14AWG is acceptable for motor leads.
Warning: 14AWG applies to motor leads only.
Power feeders to controllers
shall be governed by the fuse size included with the fan controller and/or required circuit breaker.
Electrical Installation (cont.)
Mounting the oscillator switch
Mount using the provided hardware. Select a location that is near the fan controller and so that the fan it controls is visible from the
switch location.
4 in.
(10.2 cm)
2.75 in.
(7 cm)
Summary of Contents for Pivot 180
Page 1: ...INSTALLATION GUIDE For help call 1 877 BIG FANS or visit www bigassfans com Pivot 180...
Page 46: ......
Page 48: ......
Page 50: ......
Page 59: ......