PIVOT™ 180
WWW.BIGASSFANS.COM ©2011 DELTA T CORP. ALL RIGHTS RESERVED
30
Electrical Installation (cont.)
Wiring: 100–125V/200–250V single-phase fan controllers
WARNING: Wait three minutes after disconnecting before servicing!
WARNING: Improper installation can cause electric shock or damage to the motor and controller. A qualified electrician
should perform the installation.
The diagram below shows wiring options for a 100–125V/200–250V 1Φ fan controller. See “Power Requirements for Fan Controllers”
on page 25 for detailed power requirements.
U
/T1
V
/T2
W
/T3
PE
L1
L2 L3
N
1 2 5 6
13A13B13C 14 30 16 17
25 4 11
1 2 5 6
13A13B13C 14 30 16 17
25 4 11
L1
L2
U
/T1
V
/T2
W
/T3
PE
L1
L2 L3
N
1 2 5 6
13A13B13C 14 30 16 17
25 4 11
1 2 5 6
13A13B13C 14 30 16 17
25 4 11
L1
L2
RED
BLA
CK
BL
UE
BR
OWN
BLA
CK
BLA
CK
WHITE
GR
EEN
W/ Y
EL TRACKER
G
RE
EN
W
/ YE
L TRA
CKER
RED
BLA
CK
BL
UE
BR
OWN
BLA
CK
BLA
CK
RED
GR
EEN
W/ Y
EL TRACKER
G
RE
EN
W
/ YE
L TRA
CKER
Wiring for 200–250V 1Φ, 50/60Hz fan controllers
The neutral terminal is not used when wiring the fan
controller for 200–250V 1Φ. A disconnect and EMI
filter are included with this fan controller.
Note: This fan controller does not contain fusing!
Power must be supplied to this controller via
a dedicated circuit breaker or properly fused
disconnect!
AC Input Wiring
2W plus GND
Motor Output Wiring
3W plus GND
AC Input Wiring
2W plus GND
Motor Output Wiring
3W plus GND
Optional wiring for 100–125V 1Φ, 50/60Hz fan controllers
The L2 terminal is not used when wiring the fan
controller for 100–125V 1Φ. A disconnect is included
with this fan controller.
Note: This fan controller does not contain fusing!
Power must be supplied to this controller via
a dedicated circuit breaker or properly fused
disconnect!