Short (<100 ft (30.5 m)) vs. Long (>75 ft (22.9 m)) Motor Lead Adjustment (cont.)
3. Press the Left Arrow button
to select the parameter group (
0
.00) digit.
4. Press the Up or Down Arrow button
to select the parameter group to 6 (
6
.00).
5. Press the Left Arrow button to select the parameter number (0.
00
).
6. Press the Up or Down arrow button to change the parameter numbers.
7. Once parameter 6.05 is input, press the READ/ENTER button
once.
8. As in steps 3-4, use the Up, Down, and Left Arrow buttons to change the display to read one of the following:
•
1010 (for motor lead lengths less than 100 ft (30.5 m)
•
1011 (for motor lead lengths greater than 75 ft (22.9 m)*
9. Press the READ/ENTER button again to save the changes. After this button is pressed, the parameter selection screen appears.
10. Press the PROGRAM/DISPLAY button three (3) times or until the RPM screen appears. The main LED display should read “StoP.”
Programming is complete.
* Why do the distances overlap? There is still a great deal of variability in these parameter sets. For example, either set may work for an
85 ft (25.9 m) cable run depending on motor cable properties; however, this will not always be the case.