Installation Techniques: Multiple Fan Controls
CAUTION: KBDA controllers must be installed on a branch circuit with one fused disconnect per controller and/or circuit
breaker per controller.
•
The total maximum motor lead length for all Big Ass Fan multi-fan controllers SHALL NOT EXCEED 1,200 ft (366 m).
•
MC Cable may not be used for controller output/motor leads!
•
Do not use solid core wiring of any size or insulation class for controller output/motor leads!
•
Do not connect multiple motors on a common ground return. Motors should each have a dedicated ground return back to the fan
controller. See “Grounding” on the following page.
•
Acceptable Shielded Cable types (p. 31) may be installed in long parallel runs without risk of “cross-talk” when properly installed
in a cable tray.
WARNING: This installation
method may only be used
for control boxes with
single VFDs! For control
boxes with multiple VFDs,
see above diagram. For
more information, please
contact Customer Service
at 1-877-BIG-FANS.