Installation Techniques: Single Fan Controls
CAUTION: KBDA controllers must be installed on a branch circuit with one fused disconnect per controller and/or circuit
breaker per controller.
•
The total maximum motor lead length for all Big Ass Fan single fan controllers SHALL NOT EXCEED 400 ft (122 m).
•
MC Cable may not be used for controller output/motor leads!
•
Do not use solid core wiring of any size or insulation class for controller output/motor leads!
•
Acceptable Shielded Cable types (p. 31) may be installed in long parallel runs without risk of “cross-talk” when properly installed
in a cable tray.
From Electrical
Distribution Panel
To Fan
To Fan
To Fan
From Electrical
Distribution Panel
To Fan
To Fan
To Fan