O
PERATION
C
OMFORT
A
IR
C
URTAIN
en-62
en
Multiple units operated from a single control panel.
The outputs always have a global effect: the signals are always
the same in all units connected to the control panel.
Values
V
ALUE
O
PTION
D
ESCRIPTION
0
No function
The contact is always open.
1
Error – NO
The contact is closed as soon as an error occurs.
2
Dirty filter – NO
The contact is closed as soon as the maximum filter lifespan has
expired.
3
Heating deficit
The contact is closed when the unit cannot reach the desired air tem-
perature.
4
Error or dirty filter –
NO
The contact is closed as soon as an error occurs or when the maxi-
mum filter lifespan has expired.
8
Unit on
The contact is closed as soon as the unit is switched on.
10
Error local – NO
The contact is closed as soon as an error occurs in the unit in question.
11
Fan active – NO
The contact is closed when the fans are running.
13
Heating on
The contact is closed when the unit requires heating. Use this to
switch the heating system ON or OFF via the unit.
15
Risk of freezing
The contact is closed when the temperature inside the unit drops
below 7 °C.
17
Use boost function
The contact is closed when the difference between the desired tem-
perature and the room temperature is greater than the value set for
33. Boost function
.
31
Copy input 1
The output follows the contact on input 1
32
Copy input 2
The output follows the contact on input 2
33
Copy input 3
The output follows the contact on input 3
40
Overheating protection
The contact is opened as soon as the high-limit thermostat has been
activated. (only for output 3, only for models with electrical heating)
41
Fan malfunction – NC
The contact is opened when there is a malfunction in the fan. (only for
output3, only for type L)
51
Error – NC
The contact is opened as soon as an error occurs.
52
Dirty filter – NC
The contact is opened as soon as the maximum filter lifespan has
expired.
58
Unit off
The contact is closed as soon as the unit is switched off.
60
Error local – NC
The contact is opened as soon as an error occurs in the unit in ques-
tion.
61
Fan active – NC
The contact is opened when the fans are running.
Summary of Contents for SensAir
Page 1: ...a Manual Comfort Air Curtain Model SensAir Version 1 0 North America Original Manual English ...
Page 78: ...ERRORS COMFORT AIR CURTAIN en 78 en ...
Page 82: ...MAINTENANCE COMFORT AIR CURTAIN en 82 en ...
Page 96: ...DISMANTLING COMFORT AIR CURTAIN en 96 en ...
Page 202: ...ENTRETIEN RIDEAU D AIR DE CONFORT fr 102 fr ...
Page 204: ...DÉMONTAGE RIDEAU D AIR DE CONFORT fr 104 fr ...