I
NSTALLATION
C
OMFORT
A
IR
C
URTAIN
en-30
en
2.6
Connecting the unit to the mains supply
2.6.1 Special points regarding the mains supply
For all models
Warning:
w
The unit must be earthed.
Warning:
w
The unit must be connected in accordance
with the applicable local requirements.
Maximum ratings are specified on the type
plate.
Warning:
w
Each unit must be fused in accordance with
the table below.
Fuse ratings
M
ODE
NUMBER
F
IRST
CODE
NUMBER
D
ESCRIPTION
OF
THE
SETTING
S
ECOND
CODE
NUMBER
01
02
03
04
(22)
3
Operation of air
curtain when not
heating
unheated
unheated
at standstill
(provided
that 23-8 is
set to 01)
--
(23)
8
Operation of air
curtain in defrost
mode
at standstill
unheated
(default setting)
unheated
--
M
AXIMUM
AMPERAGE
ON
TYPE
PLATE
L1, L2
OR
L3 M
AXIMUM
FUSE
VALUE
A
≤
10A
16A
≤
15A
20A
≤
20A
25A
≤
25A
35A
≤
35A
50A
≤
50A
63A
≤
65A
80A