The automatic
CHIPS
control
The
CHIPS
control automatically adjusts the strength and heat
of the unit to changing weather conditions. Thus, in all situa-
tions the energy loss is minimal and the comfort maximal.
CHIPS
stands for ‘
Corrective Heat and Impulse Prediction System
’.
Control when unit ‘on’
The unit and the auto-active control have been developed for
situations in which the door stands open.
For the most efficient climate separation and preservation of
comfort it is important that the airflow just touches the floor
and is heated sufficiently. The unit continuously measures the
values that are needed in order to achieve this:
1. The installation height (entered in the control panel)
2. The temperature difference between the two rooms:
- outdoor temperature
- room temperature
3. The temperature of the discharged air
As soon as the situation changes, the control adjusts the out-
let flow rate and the temperature of the airflow to that.
Control with unit ‘off’
If the unit is off – at night, for example – it is not active.
If it is off, the unit can indeed still perform other functions:
• The unit can be set to keep the room at a minimal ‘night’
temperature.
• Water-heated models are equipped with integrated frost
protection.
Door response
The unit and the auto-active control have been developed for
situations in which the door stands open.
If the door is not continuously open, the operation can be
adjusted to this:
• Normal operation: the unit is always active.
• Direct door response: the unit responds directly to the
opening and closing of the door.
Summary of Contents for SensAir
Page 1: ...a Manual Comfort Air Curtain Model SensAir Version 1 0 North America Original Manual English ...
Page 78: ...ERRORS COMFORT AIR CURTAIN en 78 en ...
Page 82: ...MAINTENANCE COMFORT AIR CURTAIN en 82 en ...
Page 96: ...DISMANTLING COMFORT AIR CURTAIN en 96 en ...
Page 202: ...ENTRETIEN RIDEAU D AIR DE CONFORT fr 102 fr ...
Page 204: ...DÉMONTAGE RIDEAU D AIR DE CONFORT fr 104 fr ...