46. Maximum discharge temperature
The controller limits the discharge temperature to a maxi-
mum of 50°C. Possibly set a lower value in order to save
energy.
47. Overheat protection
If the actual room temperature becomes higher than the pre-
set room temperature, the heating can be switched off in
order to prevent the room from becoming too warm.
Set the temperature above which the heating must be disabled.
Note:
n
This function can only be used if the unit is set to
automatic.
Note:
n
If this function is activated, then function
6. Minimum
air temperature
is ignored.
50. Installation height
In order to use the automatic control as efficiently as possible
and with minimum energy consumption, it is necessary to set
the installation height of the unit correctly.
Note:
n
Use values in metres.
The installation height is the distance from the floor to the
underside of the unit.
52. Nozzle angle
For optimal operation of the unit, the nozzles must be set at
the correct angle. Section 2.6
Regulating the discharge direc-
describes how the correct nozzle angle is determined.
In order to use the automatic control as efficiently as possible
and with minimum energy consumption, it is necessary to set
the nozzle angle in the control panel.
60. Function of inputs
The unit has three inputs (terminal block X520) which can be
used to enable a function to be controlled by an external
accessory such as a thermostat or a signal from a building
management system.