- 61 -
INST
ALLA
TION
COMMISSIONING
Fig. 7.32
Scroll the various parameters using keys
•
12 or 13 until the letters
Pr
that alternate
with code
10
are displayed on the LCD
display, indicating that "parameter 10"( Fig.
7.33 ) has been activated.
Fig. 7.33
Press keys
• 11
and 13 ( Fig. 7.31 ) at the
same time until the value of parameter 10
(30=180 seconds) is displayed on the LCD
display ( Fig. 7.34 ).
Fig. 7.34
It is possible to modify parameter 10 by
•
00=
0s to
99=
600s using keys
12
or
13
(each increase or reduction by a unit on
the display corresponds to 6 seconds).
By pressing key
•
11
( Fig. 7.31 ) confi rma-
tion of the inserted value is obtained.
Press keys
• 11
and 12 ( Fig. 7.31 ) at the
same time to exit without changing the val-
ue (return to the parameters list Fig. 7.33 )
Press keys
• 11
- 12 - 13 ( Fig. 7.31 ) at the
same time for 10 seconds to exit the "pro-
gramming mode".
Programming using the REMOTE control
Act on the programming of the REMOTE
control to select a minimum time between
two ignitions when the boiler functions in nor-
mal on/off heating mode.
Press button
•
for more than 3 seconds to
enter in
mode ( Fig. 7.35 ).
Fig. 7.35
0
2
1
8
1
21
1 5
6
3
9
Press buttons
•
and
at the same