background image

8

 - SELETTO- Ver. 05

D811409_05

INSTALLATION MANUAL

ENGLISH

The subsequent phases are identical for all types 

of mounting:

1)  Proceed to wiring and fixing the electronic board 

by means of the 2 screws supplied as standard, 

as shown in Fig. 2-”A”. Fully tighten the screws, 

and correct any centring errors using the slots in 

the board. Correct board positioning is obtained 

by means of the connection terminal bar, posi

-

tioned as shown in Fig. 2-”A”.

2)  Position the gasket and metal ring nut, as shown 

in Fig. 2-”B”, and proceed to fixing using the 3 

screws  supplied.  Ensure  that  the  gasket  and 

ring  nut  are  correctly  positioned,  the  ring  nut 

must have its anti-break-in dowel positioned as 

shown in Fig. 2-”C”.

3)  Attach the metal button unit after rotating it by 

about 30° anticlockwise, as shown in Fig. 2.”C”, 

then rotate it by 30° clockwise (Fig. 2.”D”). 

4)  Use the special anti-break-in setscrew wrench sup

-

plied and 

loosen the dowel until it is secured

 to 

the bottom of the push-button board (Fig. 2.”E”).

4) CONNECTION DIAGRAM

WARNING!

 In case the power is supplied by an 

external generator, it should feature a very low sa

-

fety voltage and the generator be protected against 

short-circuit and overloading.

JP1

1-2    Power  supply  input  12/24  V

~

/     ±10% 

50Hz 

      1 - + 12/24 V

~

/  

      2 - 0 V

3-4    Serial output towards control panels:    

3-TX1  4-TX2

5-6    Data  output  for  connection  to  Compass:  

5-DØ    6-D1

5) DIP-SWITCHES

DIP 1 

ON  - Connected to COMPASS system 

The  code  is  transmitted  through  outputs  5/6  to 

a  COMPASS  system  for  subsequent  check  and 

activation.

OFF   - Serial operation 

The entry of a valid code, programmed in the pushbut

-

ton panel internal memory, causes a Start signal to 

be sent through serial output TX1-TX2.

DIP 2 (only for serial operation)

ON

  - Normal operation, wait for code entry.

OFF

  - Activates the code programming mode.

JP2 

Power supply selection at 12V

~

/   or 24 V

~

/  

JP2 open

  Power supply 24V

~

/

  (Fig. 3)

JP2 closed

Power supply 12V

~

/

  (Fig. 4).

6) SELETTO PUSHBUTTON PANEL IN A COMPASS 

SYSTEM (DIP1 ON) 

Proceed to connect the SELETTO pushbutton panel, 

with reference to Fig. 4 and the specific instructions 

for the Compass system.

In  this  type  of  installation,  the  pushbutton  panel 

transmits the code typed by the user to the Compass 

control logic, which will recognise and control the 

access point. 

Therefore,  no  programming  is  required  for  the 

pushbutton panel. 

The codes are exclusively managed by the COM

-

PASS system, if necessary supported by the SE

-

CURBASE access management software. 

The limit of the codes recognised depends on the 

characteristics of the Compass system where the 

pushbutton panel is incorporated. 

Notes: 

•  Enter  the  code  quickly  during  memorisation 

(within the time allowed by Compass 485, which 

is about 5 seconds). 

•  The  code  keyed  in,  which  is  equivalent  to  a 

Compass system card code.

•  The Compass 485/232 system configuration calls 

for 3 MasterCodes to be generated (+ Code, - 

Code, Wild Card Code), which are equivalent to 

the MasterCards (+, -, Wild Card).

  During the MasterCode generation procedure, 

key in codes to replace card waving.

•  The 12V

~

/

  power supply can be obtained from 

outputs 13-16 of the 485/232 Compass system, 

which  can  supply  up  to  2  Seletto  pushbutton 

panels.

•  For  further  information,  refer  to  the  specific 

instructions for Compass use.

6.1) SETTING CODE LENGTH

You can determine the length of the codes to be 

keyed in. Choose a length of no less than 3 digits 

and no more than 6. To set, switch off “seletto” and 

switch it back on again while holding down a key 

between 3 and 6 for at least 10 secs. 

The  unit will beep to advise  you that the setting 

has been made.

Summary of Contents for SELETTO

Page 1: ...ROGRAMMABLE DIGITAL PUSHBUTTON PANEL CLAVIER NUMERIQUE PROGRAMMABLE PROGRAMMIERBARE DIGITALKNOPFTAFEL BOTONERA DIGITAL PROGRAMABLE BOTOEIRA DIGITAL PROGRAM VEL ATTENZIONE Leggere attentamente le Avver...

Page 2: ...2 SELETTO Ver 05 D811409_05...

Page 3: ...quello che non espressamente previsto in queste istruzioni non permesso Prevedere sulla rete di alimentazione dell auto mazione un interruttore o un magnetotermico onnipolare con distanza di apertura...

Page 4: ...2 solo per funzionamento seriale ON Funzionamentonormale attesadiimmissione codice OFF Attiva la modalit di programmazione dei codici JP2 Selezione alimentazione a 12V o 24 V JP2 aperto Alimentazione...

Page 5: ...zioni del quadro comando per ulteriori informazioni SeguendoloschemadiFig 3 procederealcablaggio dellalineaserialedeiquadricomandocontrollatidalla pulsantiera SELETTO utilizzando esclusivamente un dop...

Page 6: ...dici non validi il segnalatore acustico emette il segnale di errore per 60s tempo durante il quale non possibileeffettuarealtritentatividiaccesso Ogni ulteriorecodiceerratocomportaaltresegnalazio ni d...

Page 7: ...always request the assistance of qualified personnel Anything which is not expressly provided for in the present instructions is not allowed Fit an omnipolar or magnetothermal switch on the mains pow...

Page 8: ...TX1 TX2 DIP 2 only for serial operation ON Normal operation wait for code entry OFF Activates the code programming mode JP2 Power supply selection at 12V or 24 V JP2 open Power supply 24V Fig 3 JP2 c...

Page 9: ...o wire the serial line of the control panels managed by the SELETTO pushbutton panel exclusively using a telephone type line In the case where a telephone cable has several pairs of wires it is indisp...

Page 10: ...r sound for 60s during which time no other attempts at access can be made Any further incorrect code causes othererrorsignalstobeemitted withconsequent waiting time 4 Record the code numbers entered e...

Page 11: ...e d action de la motorisation Nepaslaisserdesradiocommandesoud autres dispositifs de commande port e des enfants afin d viter des actionnements involontaires de la motorisation L utilisateur doit vite...

Page 12: ...24 V 2 0 V 3 4 Sorties rielleverslescentralesdecommande 3 TX1 4 TX2 5 6 Sortie donn es pour la connexion Com pass 5 D 6 D1 5 INTERRUPTEURS DIP DIP 1 ON Connect au syst me COMPASS Le code est transmis...

Page 13: ...m me code L alimentation 24V peut tre prise des sorties 24V Alimentation des acces soires de la centrale de commande V rifier la puissance maxi absorb e par les dispositifs connect s L introduction d...

Page 14: ...la fin de la programmation reporter DIP2 sur ON 8 AVERTISSEMENTS 1 Une attente de plus de 10 s entre la composition d un chiffre et la suivante annule l introductions et doit donc tre r p t e 2 l aver...

Page 15: ...Kindern liegenlassen Sie k nnten die Anlage versehen tlich in Gang setzen Der Betreiber hat jeden Versuch eines Ein griffes oder der Reparatur zu unterlassen Nur entsprechendqualifizierteFachleutesind...

Page 16: ...Eingabe eines g ltigen Codes der im inter nen Speicher der Knopftafel abgelegt ist wird ein Startsignal ber den seriellen Ausgang TX1 TX2 geschickt DIP 2 nur f r seriellen Betrieb ON Normalbetrieb Co...

Page 17: ...elche Betriebslogik auf der Steu erplatine vorgegeben ist 2 3 4 Schritte verh lt sich die Anlage unterschiedlich Weitere Informationen entnehmen Sie bitte der Betriebsanleitung der Steuerplatine Nach...

Page 18: ...er langgezogener Ton Eingabe Enter 0 8 durchgehender kurzer Ton Fehler ung ltige Funktion 3 Werden nacheinander 5 ung ltige Codes einge geben ert nt ein Fehlersignal von 60s L nge W hrenddessen sind w...

Page 19: ...itivos de mando al alcance de los ni os para evitar el accionamiento involuntario del automatismo El usuario debe evitar cualquier intento de intervenci n o reparaci n del automatismo y dirigirse nica...

Page 20: ...P1 1 2 Entrada alimentaci n 12 24 V 10 50 Hz 1 12 24 V 2 0 V 3 4 Salida serial hacia los cuadros de man dos 3 TX 4 TX2 5 6 Salida datos para la conexi n a Com pass 5 D 6 D1 5 DIP SWITCHES DIP 1 ON Con...

Page 21: ...V Alimentaci n ac cesorios del cuadro de mandos Es necesario controlarlaabsorci nm ximadelosdispositivos conectados La introducci n de un c digo v lido comporta el env o de una orden de START en la l...

Page 22: ...sucesiva pone a cero la intro ducci n que por tanto debe repetirse 2 El indicador ac stico puede emitir 3 tipos de se alizaci n sonido breve nico introducci n num rica sonido largo introducci n Intro...

Page 23: ...tiza o N o deixe radiocomandos ou outros dispositi vos de comando ao alcance de crian as para evitar accionamentos involunt rios da automa tiza o O utilizador deve evitar qualquer tentativa de interve...

Page 24: ...uadros de comando 3 TX1 4 TX2 5 6 Sa da dados para conex o a Compass 5 D 6 D1 5 DIP SWITCH DIP 1 ON Conectado a sistema COMPASS O c digo transmitido por meio das sa das 5 6 a um sistema COMPASS para a...

Page 25: ...enta o acess rios do quadro de comando Verificar a absor o m xima dos dispositivos conectados A introdu o de um c digo v lido comporta o envio de um comando de START para a linha serial Ulteriores int...

Page 26: ...NCIAS 1 Uma espera de mais de 10 s entre a digita o de um d gito a o seguinte zera a introdu o que portanto deve ser repetida 2 O sinalizador ac stico pode emitir 3 tipos de sinaliza o som breve nico...

Page 27: ...SELETTO Ver 05 27 D811409_05 H G...

Page 28: ...28 SELETTO Ver 05 D811409_05...

Page 29: ...05 29 D811409_05 Fig 3 24V 24V SELETTO in un sistema seriale SELETTO in a serial system SELETTO dans un syst me s riel SELETTO in einem seriellen system SELETTO en un sistema serial SELETTO em um sis...

Page 30: ...30 SELETTO Ver 05 D811409_05 AWG 0 35 mm SELETTO COMPASS 485...

Page 31: ...peisen kann La alimentaci n de 12V puede obtenerse de las salidas 14 17 del Compass SC que puede alimentar hasta 2 botoneras Seletto A alimentaci n 12V pode ser obtida nas sa das 14 17 do Compass SC q...

Page 32: ...URAN A Urbaniza ao da Pedrulha Lote 9 Apartado 8123 3020 305 COIMBRA PORTUGAL tel 351 239 082 790 fax 351 239 082 799 e mail geral bftportugal com BFT S P A Via Lago di Vico 44 36015 Schio Vi Italy te...

Reviews: