22
7
> SETTING UP THE ETHERNET COUPLER
The Ethernet module is responsible for ensuring communication between the monitoring PC and
MS102. Software for monitoring PC uses the IP address of the Ethernet module to establish com-
munication. The address of the Ethernet module can be changed either by the console touch, or
by the supervisor PC itself. For more information refer to the NR 1178 PC Workstation for MS102
– Technical Manual.
7.1 > DEFAULT PARAMETERS
Default parameters are:
• IP address 192.168.94.187
• Mask
255.255.252.0
• Gate
0.0.0.0
7.2 > SETTING UP USING THE TOUCH SCREEN
To change the IP address of Ethernet coupler you should be logged in to the Master Station with the
Maintenance account. To see how to log in refer to part 10.1. Log in access. If you want to change
the IP address of the Ethernet coupler you can use the touch screen.
1. From the main page touch the MS button
or press F4.
2. Touch the Tool button or press F2.