Thermostat NO contact with centre plate, time-controlled
97-09920-000
Page 15/15
10/2011
6.2
Resistance/temperature table for remote sensor
Temperature
[°C]
10 20 25 30 40 50
Resistor [k
Ω
]
66.8 41.3 33 26.3 17.0 11.3
6.3
Troubleshooting
It becomes warm too late
Cause 1: Programmed events or time do not match.
Adjust programming.
Cause 2: A summer/wintertime changeover has taken place in the meantime (G5).
Adjust time.
Cause 3: Optimum Start H7 is deactivated or has not run long enough yet (a few days) to
determine the optimum pre-heating time.
Select Optimum Start and give the controller time to adjust itself to the conditions of the
controlling environment.
It is not possible to enter any data
Cause 1: Key lock G6 is active.
Cancel key lock.
The desired temperature cannot be set
Cause 1: Temperature limit G7 prevents the desired setting.
Reset temperature limit.
Temperature display does not change
Cause 1: Display of the set temperature G10 is activated.
Activate display of the room temperature.
6.4