background image

 

 

 
 

Thermostat NO contact with centre plate, time-controlled 

 

H3  
MIN/MAX 
FLOORTEMP 

Only when using as room thermostat with limiter. 
Setting the minimum and maximum floor temperature for the limit: 

 

LOWER LIMIT OF FLOOR TEMPERATURE

: The floor does not 

become colder than the temperature set here. 
Factory settings: 

OFF

 (no limit) 

 

UPPER LIMIT OF FLOOR TEMPERATURE

:

 

The floor does not 

become colder than the temperature set here. 
Factory setting: 

35 °C

 

Set temperatures: 

+/–

, press 

OK

 to confirm

 

  The lower temperature limit < 10 °C or the upper temperature limit 

> 40 °C must be set using 

+/–

 in order to deactivate the upper or 

lower limit with 

OFF

OFF

 is displayed. 

H4 
HEATING OR 
COOLING 

Switchover of the controller to cooling mode/heating mode 
Cooling mode only when using as room thermostat and 

H2 - 

CONTROL

 

MODE 

=

 ON/OFF

 

In cooling mode: 

 

Using the events and temperature of the heating mode 

 

H6 FROST PROTECTION 

=

 OFF 

 

H7 OPTIMUM START = NO 

Selection of cooling/heating: 

+/–

, press 

OK

 to confirm 

H5  
VALVE 
PROTECTION 

Protection of the valve against sticking after a longer absence of 
control 
The valve is opened daily at 10:00 for the time set here in minutes. 
Factory setting: 

3 min

 

Set opening time: 

+/–

, press 

OK

 to confirm 

H6  
FROST 
PROTECTION 

Setting the frost protection mode and temperature 
When frost protection is activated, the heating is activated if the 
temperature falls below the set frost protection temperature. 
Factory setting: 

5 °C

 

  Frost protection mode only possible when controller is switched 

off. 

Set temperature: 

+/–

, press 

OK

 to confirm. 

  To deactivate the frost protection with 

OFF

, set the temperature  

< 5 °C by pressing the push-button 

OFF

 is displayed. 

H7  
OPTIMUM START 

This setting causes the set setpoint temperature to be reached already 
at the start time. 

AUTO

_ is displayed in the required pre-heating time. 

Factory setting: 

YES

 

Set 

YES

 (OPTIMUM START)/

NO

+/–

, press 

OK

 to confirm 

H8  
VALVES NORMALLY 
OPEN 

Switchover of the relay switching behaviour opened for using actuators 
currentless 
Factory setting: 

NO

 (deactivated) 

Select: 

YES

 (activated)/

NO

+/–

, press 

OK

 to confirm 

H9  
ENERGY COUNTER 
RESET 

Resetting the energy costs counter set under 

G8/G9

 to 0 

Select 

YES

 (reset): 

+/–

, press 

OK

 to confirm

 

H10  
DISPLAY FLOOR 
TEMPERATURE 

Only when using as room thermostat with limiter. 
Display of the current floor temperature for service purposes 
--- 

 

 
97-09920-000

 

 

Page 13/15 

10/2011

Summary of Contents for 2044 Series

Page 1: ...mpliant with the guidelines of the EN 60730 and works according to the mode of operation 1C Failure to comply with these instructions may result in damage to the device fire or other hazards These ope...

Page 2: ...ater is switched on if the room temperature falls below the preset default value Floor thermostat The floor temperature is controlled The heating is switched on if the room temperature measured by the...

Page 3: ...s using the 9 10 push button if required and press Info OK 11 to confirm Settings The selection of the settings menus is confirmed Carry out further settings with the 9 10 push button and press Info O...

Page 4: ...the morning and night setback Mon Fri Sat Sun Event C C 1 6 00 21 0 7 00 21 0 2 8 30 18 0 10 00 18 0 3 12 00 21 0 12 00 21 0 4 14 00 18 0 14 00 21 0 5 17 00 21 0 17 00 21 0 6 22 00 15 0 Sat 23 00 Sun...

Page 5: ...USER SETTING with push button 9 10 and press OK to confirm see operating thermostat G 1 PROGRAM SELECT ONE is displayed Press OK The number of the active program flashes Using select the desired progr...

Page 6: ...me in the display is saved as the start time of the next interval If flashes in the display then the following event is on the next weekday If OK is pressed the display for the start time changes to t...

Page 7: ...ters of the set program day profile The presettings of the program correspond to the current day program of Monday Set temperature and events confirm each setting by pressing OK Activation with confir...

Page 8: ...e electrician Select YES NO heating off on press OK to confirm Display of function 16 OFF Switch on controller again Select any function via the menu or keep Menu s pressed down for 10 s G5 SUMMER WIN...

Page 9: ...R TEMPERATURE Only when using as floor temperature controller Activating the display of the floor temperature as information number The display C is hidden Factory setting NO normal temperature displa...

Page 10: ...To enable optimum room temperature control using the internal sensor the installation location selected should allow free air circulation not be located behind curtains cupboards shelves etc not be ex...

Page 11: ...ipe so that it can be replaced later The wire of the temperature sensor supplies mains voltage and can be extended to 50 m using suitable wires To avoid signal disturbances do not lay the wire of the...

Page 12: ...Operation H1 APPLICATION Selecting between the thermostat processes according to heating type ROOM Room thermostat FLOOR Floor thermostat LIMITER Room thermostat with limiter Factory settings ROOM Whe...

Page 13: ...ve is opened daily at 10 00 for the time set here in minutes Factory setting 3 min Set opening time press OK to confirm H6 FROST PROTECTION Setting the frost protection mode and temperature When frost...

Page 14: ...itch off voltage and switch on again ERR EXT SENSOR Failure short circuit of the external temperature sensor Replace temperature sensor Display range exceeded fallen short of 6 Appendix 6 1 Specificat...

Page 15: ...vironment It is not possible to enter any data Cause 1 Key lock G6 is active Cancel key lock The desired temperature cannot be set Cause 1 Temperature limit G7 prevents the desired setting Reset tempe...

Reviews: