Thermostat NO contact with centre plate, time-controlled 

Setting the heating type 

When commissioning the controller, the heating type must be set. 
The device is in the basic display. 

„

  Press 

Menu/

s

 (8) push-button. 

A help text is shown at the bottom of the display. 

„

  Keep pressing the 

+/–

 push-button repeatedly until 

INSTALLER SETTINGS

 is displayed. 

„

  Press 

OK

CODE 

is displayed and the code number 

0

 flashes. 

„

  Select code number using 

7

 

+/–

 and press 

OK

 to confirm. 

H1 

and the scrolled text of

 APPLICATION 

is displayed. 

„

  Press 

OK

„

  Set the desired temperature using 

+/–

 and press 

OK

 to confirm. 

 

ROOM 

is preset. When changing the heating type, all user and installer settings are reset 

to the factory settings. 

Overview and selection of the settings 

The settings menu is invoked (see Setting heating type). If 

H1

 and the scrolled text of 

APPLICATION

 is displayed, you can toggle between the possible settings menus using 

+

/

 

(see Table 3). 

 

Setting 

Description 

Operation 

H1  
APPLICATION 

Selecting between the thermostat processes according to heating type:

ROOM 

= Room thermostat 

FLOOR

 = Floor thermostat 

LIMITER

 = Room thermostat  with limiter 

Factory settings: 

ROOM

 

When used as a room thermostat, it is also possible to set whether an 
external temperature sensor 

(EXTERNAL SENSOR = YES)

 is 

connected. 
Selection of the heating type: 

+/–

, press 

OK

 to confirm 

H2  
CONTROL MODE 

Selection of the control type: 

 

PWM 

(Pulse width modulation) with adjustment option for cycle 

time. Select short cycle time for fast heating systems and long 
cycle time for slow heating systems. 
Factory setting of cycle time: 

10 min 

The minimum switch on/off time is 10 % of the cycle time. 

 

ON/OFF 

(on-off control) with the setting option of hysteresis and 

minimum switch on/off time of the relay 
Factory setting hysteresis: 

OFF

 

Factory setting minimum switch on/off time: 

10 min

 

  If no hysteresis is set, the relay switches with the set minimum 

switch on/off time even in the case of very small temperature 
differences. 

Selection of controller, cycle time, hysteresis, switch on/off time: 

+/–

press 

OK

 to confirm 

 

 
97-09920-000

 

 

Page 12/15 

10/2011

Summary of Contents for 2044 Series

Page 1: ...mpliant with the guidelines of the EN 60730 and works according to the mode of operation 1C Failure to comply with these instructions may result in damage to the device fire or other hazards These ope...

Page 2: ...ater is switched on if the room temperature falls below the preset default value Floor thermostat The floor temperature is controlled The heating is switched on if the room temperature measured by the...

Page 3: ...s using the 9 10 push button if required and press Info OK 11 to confirm Settings The selection of the settings menus is confirmed Carry out further settings with the 9 10 push button and press Info O...

Page 4: ...the morning and night setback Mon Fri Sat Sun Event C C 1 6 00 21 0 7 00 21 0 2 8 30 18 0 10 00 18 0 3 12 00 21 0 12 00 21 0 4 14 00 18 0 14 00 21 0 5 17 00 21 0 17 00 21 0 6 22 00 15 0 Sat 23 00 Sun...

Page 5: ...USER SETTING with push button 9 10 and press OK to confirm see operating thermostat G 1 PROGRAM SELECT ONE is displayed Press OK The number of the active program flashes Using select the desired progr...

Page 6: ...me in the display is saved as the start time of the next interval If flashes in the display then the following event is on the next weekday If OK is pressed the display for the start time changes to t...

Page 7: ...ters of the set program day profile The presettings of the program correspond to the current day program of Monday Set temperature and events confirm each setting by pressing OK Activation with confir...

Page 8: ...e electrician Select YES NO heating off on press OK to confirm Display of function 16 OFF Switch on controller again Select any function via the menu or keep Menu s pressed down for 10 s G5 SUMMER WIN...

Page 9: ...R TEMPERATURE Only when using as floor temperature controller Activating the display of the floor temperature as information number The display C is hidden Factory setting NO normal temperature displa...

Page 10: ...To enable optimum room temperature control using the internal sensor the installation location selected should allow free air circulation not be located behind curtains cupboards shelves etc not be ex...

Page 11: ...ipe so that it can be replaced later The wire of the temperature sensor supplies mains voltage and can be extended to 50 m using suitable wires To avoid signal disturbances do not lay the wire of the...

Page 12: ...Operation H1 APPLICATION Selecting between the thermostat processes according to heating type ROOM Room thermostat FLOOR Floor thermostat LIMITER Room thermostat with limiter Factory settings ROOM Whe...

Page 13: ...ve is opened daily at 10 00 for the time set here in minutes Factory setting 3 min Set opening time press OK to confirm H6 FROST PROTECTION Setting the frost protection mode and temperature When frost...

Page 14: ...itch off voltage and switch on again ERR EXT SENSOR Failure short circuit of the external temperature sensor Replace temperature sensor Display range exceeded fallen short of 6 Appendix 6 1 Specificat...

Page 15: ...vironment It is not possible to enter any data Cause 1 Key lock G6 is active Cancel key lock The desired temperature cannot be set Cause 1 Temperature limit G7 prevents the desired setting Reset tempe...

Reviews: