background image

17

When using a phase-phase power supply, use a tester to determine
which of the two wires has the greater potential compared to the
earth and connect it to the L terminal.  Connect the remaining wire to
the N terminal.

For floating power supplies, that is, those that have no earth con-
nection, an insulation transformer must be used, with a secondary
unit connected to the earth.

The following are obligatory:
- A multi-pole trip-switch must be used to disconnect the line, that
conforms to the CEI-EN 60335-1 standards (contact opening at
least 3,5mm, category III).

- Use cables with a 1,5 mm

2

 section and respect the L (Phase) –

N (Neutral) connection.
- The amperage on the switch must be adequate for the boiler’s
electrical power rating – see the technical data to check the elec-
trical power rating for the model installed.
- Connect the equipment to an efficient earthing system.
- The power socket must be inaccessible after installation.

The use of gas or water pipes to earth this equipment is forbidden.

The manufacturer does not accept any responsibility for any dam-
age caused due to the lack of a proper earth or failure to comply
with the wiring diagram.

CONNECTING THE SYSTEM CONTROL BOARD TO THE CON-
NECT AT/BT CONNECTION BOX TERMINAL BOARD

Use the cables provided in the kit, and follow the instructions below:
1. 5-pole low temperature control cable
2. High temperature control cable with prods.
3. Screened signal cable with 2-pole connector.

1.5-pole low temperature control cable

FIG. 14a-14b

1. 5-pole low temperature control cable

Connect the 5-pole connector to the electronic system control
board.

FIG. 15a-15b

2. High temperature pump control cable with prods.

Connect the two prods to the boiler’s terminal board

FIG. 16a-16b

3. Screened signal cable with 2-pole connector.

Connect the NTC sensor connector on the electronic system
control board end.
Connect the two prods for the low temperature limit thermostat
to the boiler’s terminal board

FIG. 17

Connect the shielded cable connector (on the Connect part) to
the NTC (3) probe and the other 2 terminal clips to the 2
thermostats, jumpering them with the jumper on the cable (fig.
18).

INSTRUCTION TO  RESET THE  MANUAL  HIGH  LIMIT
THERMOSTAT INTERVENTION

The permanent signal of 77 flashing alarm (refer to the boiler i
nstrucions) may  be caused by the manual high limit thermostat
intervention.
T. intervention  63°C.
If the 77 alarm is permanent operate as follows:

FIG. 18

- open the front cover of the Connect
- push the red button on the thermostat positionned on the pipe
- verify tha the 77 signal desappears after a while
- close the front cover of the Connect

If signal 77 is still displaied wait to the cooling of the system before
a new attempt the unlock.

CONNECTING THE  CONNECT  AT/BT TO THE  ELECTRICITY
MAINS

FIG. 19

Connect the Connect AT/BT unit to the electricity mains (phase /
neutral / earth) using the cable supplied.

Drawing the power supply for the Connect AT/BT from the
boiler is absolutely forbidden as the boiler’s fuse is not sized
to take the electrical loads associated with the Connect AT/BT.

CONNECTING THE  AMBIENT THERMOSTAT  (TA)

FIG. 12a-12b

Boilers from inside only: The TA of the low temperature system is
connected to terminal M2A

Boilers from outside only: The TA of the low temperature system
is connected to terminal C4P
The TA for the low temperature system must be connected to termi-
nal M2A.

CONNECTING THE EXTERNAL SENSOR

Connect the external sensor to the boiler as indicated in the in-
struction manual for the boiler.

FIRST STARTING UP

Before switching the Connect AT/BT on, check that the electrical
and plumbing connections have been formed correctly.

FIG. 17

During testing, the temperatures can be checked due to the two
thermometers.

CIRCULATION PUMPS

The Connect AT/BT is supplied with circulation units with a three-
speed control.
Choose the best speed to suit the specific characteristics of the
systems.

RELEASING THE PUMPS IF NECESSARY

If the unit has been inactive for a lengthy period of time and the
circulation units are stuck, unscrew the caps on the front and turn
the shaft for the circulation unit motor using a screwdriver.
Do this extremely carefully so as not to damage the components
themselves.

THREE-WAY MIXING VALVE

If the unit has been inactive for a lengthy period of time and the

MIXER VALVE

 is stuck, activate the lever in the motor by hand, in

order to release the gate in the valve.

PROGRAMMING PARAMETERS

To set the parameters for working with the Connect AT/BT:
Access the boiler’s programmable parameters as indicated in the
“programming parameters” chapter of the boiler’s instruction
manual.

Heating mode

Select parameter 20 (heating mode), choose option 6 (Connect
AT/BT) and confirm it.

Responsiveness of the external sensor

Select parameter 65 (responsiveness of the external sensor) to suit
the needs and characteristics of the installation, as described in the
boiler manual.

Summary of Contents for 1102539

Page 1: ...I K ZIK TI K ZIK TI K ZIK NY NY NY NY NYV SZEREL KNEK S V SZEREL KNEK S V SZEREL KNEK S V SZEREL KNEK S V SZEREL KNEK S M RKASZER M RKASZER M RKASZER M RKASZER M RKASZERVIZ R SZ RE VIZ R SZ RE VIZ R S...

Page 2: ...2 ambient thermostat IBT Low temperature system mixed IAT High temperat system SOE Sonda Zewn TA1 TA2 TAWT TABT IBT Strefa NT IAT Strefa WT SOE Sonda exterior TA1 TA2 termostato ambiente IBT instalaci...

Page 3: ...23 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 1...

Page 4: ...L F2 MR BL MR BL MR BL G V MA RA 12a M2A C4P TABT NE NE MR BL F2 MR BL MR BL MR BL NE NE C4P C4P Boilers from inside Boilers from outside Boilers from inside Boilers from outside Boilers from inside B...

Page 5: ...outside Boilers from inside Boilers from outside Boilers from inside Boilers from outside Boilers from inside boilers from outside Caldaie da interno caldaie da esterno Chaudi re d int rieur chaudi re...

Page 6: ...F2 Olvad biztos t k 2AF MA MA MA MA MA kieg sz t kapocssor RA RA RA RA RA fagyv delmi elektromos ellen ll s F F F F FA A A A A F zis MC MC MC MC MC Z rt kever szelep MO MO MO MO MO Nyitott kever szel...

Page 7: ...tto nei nostri stabilimenti viene costruito facendo attenzione anche ai singoli componenti in modo da proteggere sia l utente che l installatore da eventuali inci denti Si raccomanda quindi al persona...

Page 8: ...izzando una nicchia di contenimento adatta alle dimensioni del Connect AT BT ed allo spessore della parete valori indicativi minimi riportati in figura posizionare Connect AT BT nella propria sede ric...

Page 9: ...conforme alle Norme CEI EN 60335 1 apertura dei contatti di almeno 3 5mm categoria III Utilizzare cavi di sezione 1 5mm2 e rispettare il colle gamento L Fase N Neutro L amperaggio dell interruttore de...

Page 10: ...daia Selezione MAX Set point riscaldamento circuito bassa tempe ratura Entrare nel parametro 31 MAX Set point selezionando il valore scelto in base all esigenze e caratteristiche dell installazione e...

Page 11: ...re Connect AT BT peut tre encastr ce qui limine tout encombrement ext rieur ou mont au mur suspendu Il peut tre plac proximit de la chaudi re ou distance condition que la longueur des raccordements h...

Page 12: ...ravaux d encastrement du dispositif Les branchements lectriques et les raccordements hydrauliques entre l installation et le Connect AT BT doivent tre r alis s l int rieur du dispositif vous devez tou...

Page 13: ...IRCULATION Connect AT BT est quip de circulateurs munis de r gulateur trois vitesses Choisissez la vitesse opportune en fonction des caract ristiques sp cifiques des installations D VERROUILLAGE VENTU...

Page 14: ...re 32 Point de consigne MINI en s lec tionnant la valeur en fonction des besoins et des caract ristiques de l installation et de la courbe climatique configur e auparavant consultez aussi le mode d em...

Page 15: ...any accidents We therefore urge trained personnel to be particularly careful with the elec trical connections on completion of each job done on the product especially as far as the bare parts of the...

Page 16: ...m and the conduiting for the electric cables Electrical protection level IPX4D FIG 4 TYPICAL INSTALLATION LAYOUT The figure alongside shows a possible way of installing the Connect AT BT NOTE To allow...

Page 17: ...T intervention 63 C If the 77 alarm is permanent operate as follows FIG 18 open the front cover of the Connect push the red button on the thermostat positionned on the pipe verify tha the 77 signal d...

Page 18: ...the value chosen to suit the needs and characteristics of the installation and the climatic curve set previously also see the boiler manual SETTING THE HEATING TEMPERATURE WHEN USING HEAT REGULATION I...

Page 19: ...G LNE I BEZPIECZE STW GI OG LNE I BEZPIECZE STW GI OG LNE I BEZPIECZE STW GI OG LNE I BEZPIECZE STWO O O O O Urz dzenie wyprodukowane w naszych zak adach jest skonstruowane w spos b zabezpieczaj cy u...

Page 20: ...ny zgodnie z za czonym rysunkiem Pod czenia mog by wykonane bezpo rednio wykorzystuj c przy cza e skie obecne na rurach zasilania i powrotu zestawu lub poprzez zawory odcinaj ce nie dostarczone na wyp...

Page 21: ...CZENI Y CZENI Y CZENI Y CZENIA A A A A TERMOREG TERMOREG TERMOREG TERMOREG TERMOREG W przypadku kiedy nie s aktywne termoregulacje obydw ch stref nale y temperatur na co strefy niskiej wybra bezpo red...

Page 22: ...iskiej temperatury Je li cho jedna z kontroli da negatywny wynik to instalacja nie mo e by uruchomiona K K K K KONSEWR ONSEWR ONSEWR ONSEWR ONSEWRW W W W WA A A A ACJ CJ CJ CJ CJA A A A A Przed wykona...

Page 23: ...necesarios para la conexi n a la caldera en el caso de la instalaci n t pica del Connect AT BT cerca de la caldera longitud de los cables 2 m ADVERTENCIAS Y SEGURIDADES El aparato producido en nuestra...

Page 24: ...eveer las obras de alba iler a realizando un hueco adecuado a las dimensiones de Connect AT BT y al espesor de la pared valores indicativos m nimos expuestos en la figura colocar Connect AT BT en su p...

Page 25: ...ra la gesti n de la baja temperatura con 5 polos conectar en el lado de la tarjeta electr nica para la gesti n de la instalaci n el conector de 5 polos FIG 15a 15b FIG 15a 15b FIG 15a 15b FIG 15a 15b...

Page 26: ...ciones clim ticas de la zona geogr fica hacer referencia tambi n al manual de la caldera Selecci n MAX del Set point de la calefacci n para el circuito de baja temperatura Entrar en el par metro 31 MA...

Page 27: ...nhoz val sszek t shez sz ks ges vezet kek a k sz l kkel egy tt ker lnek lesz ll t sra arra az esetre ha a Connect AT BT t a kaz nhoz k zel ker l felszerel sre vezet kek hossza 2m FIGY FIGY FIGY FIGY...

Page 28: ...9b FIG 9a 9b FIG 9a 9b FIG 9a 9b FIG 9a 9b 3 Csatlakoztassa a lapos szalagk belt a berendez s s a kaz nir ny t elektromos panelhoz az 1 k p s az elektromos bra alapj n FIG 10a 10b FIG 10a 10b FIG 10a...

Page 29: ...SET N A villog 77 v szjelz s lland vil g t sa a kaz n haszn lati k zik nyv nek figyelembe v tel vel a k zi visszakapcsol s hat rol termoszt t m k d sbe l p s t jelentheti A m k d sbe l p s h m rs klet...

Page 30: ...klet f t k r MAX Set pontj nak be ll t sa Az alacsony h m rs klet f t k r MAX Set pontj nak be ll t sa Az alacsony h m rs klet f t k r MAX Set pontj nak be ll t sa L pjen a 31 param terbe MAX Set pont...

Page 31: ...at utilizatorul cat si instalatorul de eventualele ac cidente De aceea rugam personalul calificat sa acorde o atentie deosebita conexiunior electrice la finalizarea fiecarei interventii asupra produsu...

Page 32: ...itivului pozitionati intai unitatea Connect AT BT apoi conductele de intrare si iesire ale sistemului si in final cablurile electrice Nivel de protectie electrica IPX4D FIG FIG FIG FIG FIG 4 SCHEMA GE...

Page 33: ...ELIBERAREA POMPELOR DACA ESTE NECESAR ELIBERAREA POMPELOR DACA ESTE NECESAR Daca unitatea a fost inactiva o perioada lunga de timp si unitatile de circulatie sunt blocate desfaceti capacele frontale...

Page 34: ...a punctului de setare MAX pentru incalzire circuit tem Selectarea punctului de setare MAX pentru incalzire circuit tem Selectarea punctului de setare MAX pentru incalzire circuit tem peratura redusa p...

Page 35: ...dhold efter udpakning Alle vore kedler er produceret med omhu for hver enkelt komponent for at undg at forvolde skade p bruger og installat rer Det er meget vigtigt at alle el forbindelser foretages o...

Page 36: ...rbindelserne foretages Elektrisk beskyttelse IPX4D FIG 4 STANDARD INSTALLATION Tegningen viser et eksempel p installation af CONNECT AT BT Bem rk Der skal afs ttes plads til installation af haner medf...

Page 37: ...ller neds ttes i henhold til den beregnede v rdi ndre varme indstilling Korrektionen kan foretages mellem komfort niveauer 5 og 5 INDSTILLING AF ANL GSTEMPERATUR N R VARMEREGULERING IKKE ANVENDES Fixe...

Page 38: ...punkt for det relevante kredsl b KONTROL EFTER INSTALLATION Kontroller anl gstrykket Kontroller der er tilsluttet str m T thedspr v installationen Kontroller at r r og el forbindelser er foretaget ko...

Page 39: ...ja w cianie IPX4D L szeroko 440 mm P g boko 160 mm H wysoko 616 mm Waga netto 16 Kg Maksymalne ci nienie 3 bar Alimentaci n el ctrica 230 10 50 V Hz Potencia m xima consumida por el Connect AT BT 230...

Page 40: ...w r mieszaj cy 11 Puszka po cze elektrycznych 1 Termostato l mite de la instalaci n de baja temperatura con rearme autom tico 2 Termostato l mite de la instalaci n de baja temperatura con rearme manua...

Page 41: ...e powinna przekracza 15 m okablowanie na wyposa eniu ma d ugo 2m CONEXIONES HIDR ULICAS E Impulsi n caldera 3 4 U Retorno caldera 3 4 MD Impulsi n circuito calefacci n 3 4 Mmix Alimentaci n de la inst...

Page 42: ...E INSTALLATION BASSE TEMP RATURE 1 premi re vitesse 2 deuxi me vitesse 3 troisi me vitesse 3A 1A premi re vitesse avec vanne mix ferm e 1A premi re vitesse avec vanne mix ouverte 2A deuxi me vitesse a...

Page 43: ...t gy jt egys geibe 1 Els sebess g 2 M sodik sebess g 3 Harmadik sebess g A VARF REZIDUAL CIRCULATOR SISTEM TEMPERATURA RIDICATA B Capacitate instalatie l h C Varf rezidual m C A D VARF REZIDUAL CIRCUL...

Page 44: ...V MR BL MR BL MR BL NE NE MR BL F2 G V MA RA MMV N Boilers from inside Boilers from outside Boilers from inside boilers from outside Caldaie da interno caldaie da esterno Chaudi res d int rieur chaudi...

Page 45: ...MC MIX cerrado MO MIX abierto NM neutro mix N neutro PBT Bomba B T PAT Bomba A T TLA termostato l mite baja temp rearme autom tico TLM termostato l mite baja temp rearme manual SO sonda SOE sonda exte...

Page 46: ...46...

Page 47: ......

Page 48: ...Cod 10028768 Ed 1 35 06...

Reviews: