For your safety, remember that:

The boiler should not be used by children or people that are
unable to use it properly.

It is dangerous to activate devices or electrical equipment
such as switches, domestic appliances, etc. if you smell any
fuel or burning.

Should a gas leak occur, ventilate the room by opening the
doors and windows, shut the main gas valve, call in
professionally qualified personnel from the Technical Assist-
ance service immediately.

Do not touch the boiler when barefoot or when parts of your
body are wet or damp.

Before cleaning, disconnect the boiler from the electricity
mains by switching the bi-pole switch for the plant and the
main switch on the control panel to “OFF”.

Any modifications to the safety and regulating devices without
prior authorisation or instructions from the manufacturer are
forbidden.

Do not pull on, disconnect, or twist the electrical cables that
come from the boiler, even when it is disconnected from the
electricity mains.

Do not block up or reduce the size of ventilation openings in
the room in which the unit is installed.

Do not leave containers or inflammable substances in the
room in which the equipment is installed.

Do not leave any part of the packing within reach of children.

INSTALLATION OF THE APPLIANCE

FIG. 1

  The Connect AT/BT can be wall-mounted or “built-in”, and

can be located near the boiler or at a distance, provided the length
of the plumbing and electrical connections between the boiler and
the Connect AT/BT unit do not exceed 15 metres.
The Connect AT/BT can be installed in positions exposed to the
weather (rain, sun, ice, etc.) only if in  “built-in” installation.

Note: 

The wiring supplied is 2 metres long.

FIG. 2  Wall-mounted installation

When the Connect AT/BT is wall-mounted it must be supported by
two expanding wall anchors (supplied) that are suitable for the
type of wall and weight of the equipment.
We recommend using pipe sleeves built into the wall in order to
limit the infiltration of water.
These pipe sleeves are not supplied with the unit.
Electrical protection level IP10D.

FIG. 3  “Built-in” installation

When the Connect AT/BT unit is built-in:
- Provide the building work, complete with a niche of suitable

size for the Connect AT/BT, to suit the thickness of the wall
(minimum indicative dimensions shown in the figure).

- Position the Connect AT/BT in position, and remember to open

out the two support lugs to fix it more securely.

- Protect the side edges and front while building in the device.
Since the plumbing and electrical connections between the system
and the Connect AT/BT must be contained within the overall size
of the device itself, first position the Connect AT/BT and then the
entry and exit pipes for the system and the conduiting for the electric
cables.
Electrical protection level IPX4D.

FIG. 4  TYPICAL INSTALLATION LAYOUT
The figure alongside shows a possible way of installing the
Connect AT/BT.

NOTE: 

To allow for installing taps (not supplied) a niche must be

formed of sufficient size to allow them to be fitted below the Connect
AT/BT itself.

HYDRAULIC CONNECTIONS

Before forming the connections all the piping must be thoroughly
flushes to remove any residue that could compromise the proper
functioning of the Connect AT/BT.

FIG. 5

The plumbing connections to the boiler and the system must be
carried out rationally, as indicated in the figure.
Direct connections can be formed using the female couplings on
the delivery and return pipes for the Connect AT/BT, or taps (not
supplied) can be fitted on the lines for shutting off the lines.
These taps are very useful when maintenance is carried out, as
they allow the Connect AT/BT to be drained without having to drain
the entire system.

Check that the expansion vessel on the boiler has suffi-
cient capacity for the size of the system.

FIG. 6

Once the Connect AT/BT has been installed, the 2 ramps supplied
(along with their seals) that interface with the boiler centres must
be fitted inside the Connect AT/BT.

ELECTRIC CONNECTIONS

To form the electrical connections for the Connect AT/BT, access
must be obtained to the Connect AT/BT and the boiler card.

FIG. 7  

To gain access to the Connect AT/BT:

- Remove the front cover panel from the Connect AT/BT

If you decide to use cables other than those supplied, cables with
a 0,50 mm

2

 section must be used.  The length of these connections

must not exceed 15 metres.

CONNECTING THE ELECTRONIC SYSTEM CONTROL BOARD
(supplied) TO THE  BOILER’S  ELECTRONIC  BOARD

This connection must be formed using the correct flat cable
(supplied).
The electronic system control board must also be powered by the
mains power supply.

Prevent cables from coming into contact with anti-freeze
resistances.

To form the connection, proceed as follows:

1. Remove the boiler’s cover, open the back cover on the control

panel, as shown in the manual for the boiler.

FIG. 8a-8b

2. Insert the electronic system control board supplied (C) into its

seating inside the control panel, as shown in figure 2.

FIG. 9a-9b

3. Connect the flat cable to the electronic system control board and

the electronic boiler control board (see photo 1 and the wiring
diagram).

FIG. 10a-10b

4. To provide power to the electronic system control board, con-

nect the cable’s four-pole connector (supplied), as shown in
photo 2

FIG. 11

Pass the wiring harness between the plastic of the instrument
panel and the fuse carrier

FIG. 12a-12b

Connect the prods to the mains power supply.
Blue wire - neutral
Brown wire - phase
(see the wiring diagram)

FIG. 13

5. Boilers from inside only: insert the two-pole terminal M2A for the
ambient thermostat below the power supply terminal board in the
boiler’s console.

Summary of Contents for 1102539

Page 1: ...I K ZIK TI K ZIK TI K ZIK NY NY NY NY NYV SZEREL KNEK S V SZEREL KNEK S V SZEREL KNEK S V SZEREL KNEK S V SZEREL KNEK S M RKASZER M RKASZER M RKASZER M RKASZER M RKASZERVIZ R SZ RE VIZ R SZ RE VIZ R S...

Page 2: ...2 ambient thermostat IBT Low temperature system mixed IAT High temperat system SOE Sonda Zewn TA1 TA2 TAWT TABT IBT Strefa NT IAT Strefa WT SOE Sonda exterior TA1 TA2 termostato ambiente IBT instalaci...

Page 3: ...23 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 1...

Page 4: ...L F2 MR BL MR BL MR BL G V MA RA 12a M2A C4P TABT NE NE MR BL F2 MR BL MR BL MR BL NE NE C4P C4P Boilers from inside Boilers from outside Boilers from inside Boilers from outside Boilers from inside B...

Page 5: ...outside Boilers from inside Boilers from outside Boilers from inside Boilers from outside Boilers from inside boilers from outside Caldaie da interno caldaie da esterno Chaudi re d int rieur chaudi re...

Page 6: ...F2 Olvad biztos t k 2AF MA MA MA MA MA kieg sz t kapocssor RA RA RA RA RA fagyv delmi elektromos ellen ll s F F F F FA A A A A F zis MC MC MC MC MC Z rt kever szelep MO MO MO MO MO Nyitott kever szel...

Page 7: ...tto nei nostri stabilimenti viene costruito facendo attenzione anche ai singoli componenti in modo da proteggere sia l utente che l installatore da eventuali inci denti Si raccomanda quindi al persona...

Page 8: ...izzando una nicchia di contenimento adatta alle dimensioni del Connect AT BT ed allo spessore della parete valori indicativi minimi riportati in figura posizionare Connect AT BT nella propria sede ric...

Page 9: ...conforme alle Norme CEI EN 60335 1 apertura dei contatti di almeno 3 5mm categoria III Utilizzare cavi di sezione 1 5mm2 e rispettare il colle gamento L Fase N Neutro L amperaggio dell interruttore de...

Page 10: ...daia Selezione MAX Set point riscaldamento circuito bassa tempe ratura Entrare nel parametro 31 MAX Set point selezionando il valore scelto in base all esigenze e caratteristiche dell installazione e...

Page 11: ...re Connect AT BT peut tre encastr ce qui limine tout encombrement ext rieur ou mont au mur suspendu Il peut tre plac proximit de la chaudi re ou distance condition que la longueur des raccordements h...

Page 12: ...ravaux d encastrement du dispositif Les branchements lectriques et les raccordements hydrauliques entre l installation et le Connect AT BT doivent tre r alis s l int rieur du dispositif vous devez tou...

Page 13: ...IRCULATION Connect AT BT est quip de circulateurs munis de r gulateur trois vitesses Choisissez la vitesse opportune en fonction des caract ristiques sp cifiques des installations D VERROUILLAGE VENTU...

Page 14: ...re 32 Point de consigne MINI en s lec tionnant la valeur en fonction des besoins et des caract ristiques de l installation et de la courbe climatique configur e auparavant consultez aussi le mode d em...

Page 15: ...any accidents We therefore urge trained personnel to be particularly careful with the elec trical connections on completion of each job done on the product especially as far as the bare parts of the...

Page 16: ...m and the conduiting for the electric cables Electrical protection level IPX4D FIG 4 TYPICAL INSTALLATION LAYOUT The figure alongside shows a possible way of installing the Connect AT BT NOTE To allow...

Page 17: ...T intervention 63 C If the 77 alarm is permanent operate as follows FIG 18 open the front cover of the Connect push the red button on the thermostat positionned on the pipe verify tha the 77 signal d...

Page 18: ...the value chosen to suit the needs and characteristics of the installation and the climatic curve set previously also see the boiler manual SETTING THE HEATING TEMPERATURE WHEN USING HEAT REGULATION I...

Page 19: ...G LNE I BEZPIECZE STW GI OG LNE I BEZPIECZE STW GI OG LNE I BEZPIECZE STW GI OG LNE I BEZPIECZE STWO O O O O Urz dzenie wyprodukowane w naszych zak adach jest skonstruowane w spos b zabezpieczaj cy u...

Page 20: ...ny zgodnie z za czonym rysunkiem Pod czenia mog by wykonane bezpo rednio wykorzystuj c przy cza e skie obecne na rurach zasilania i powrotu zestawu lub poprzez zawory odcinaj ce nie dostarczone na wyp...

Page 21: ...CZENI Y CZENI Y CZENI Y CZENIA A A A A TERMOREG TERMOREG TERMOREG TERMOREG TERMOREG W przypadku kiedy nie s aktywne termoregulacje obydw ch stref nale y temperatur na co strefy niskiej wybra bezpo red...

Page 22: ...iskiej temperatury Je li cho jedna z kontroli da negatywny wynik to instalacja nie mo e by uruchomiona K K K K KONSEWR ONSEWR ONSEWR ONSEWR ONSEWRW W W W WA A A A ACJ CJ CJ CJ CJA A A A A Przed wykona...

Page 23: ...necesarios para la conexi n a la caldera en el caso de la instalaci n t pica del Connect AT BT cerca de la caldera longitud de los cables 2 m ADVERTENCIAS Y SEGURIDADES El aparato producido en nuestra...

Page 24: ...eveer las obras de alba iler a realizando un hueco adecuado a las dimensiones de Connect AT BT y al espesor de la pared valores indicativos m nimos expuestos en la figura colocar Connect AT BT en su p...

Page 25: ...ra la gesti n de la baja temperatura con 5 polos conectar en el lado de la tarjeta electr nica para la gesti n de la instalaci n el conector de 5 polos FIG 15a 15b FIG 15a 15b FIG 15a 15b FIG 15a 15b...

Page 26: ...ciones clim ticas de la zona geogr fica hacer referencia tambi n al manual de la caldera Selecci n MAX del Set point de la calefacci n para el circuito de baja temperatura Entrar en el par metro 31 MA...

Page 27: ...nhoz val sszek t shez sz ks ges vezet kek a k sz l kkel egy tt ker lnek lesz ll t sra arra az esetre ha a Connect AT BT t a kaz nhoz k zel ker l felszerel sre vezet kek hossza 2m FIGY FIGY FIGY FIGY...

Page 28: ...9b FIG 9a 9b FIG 9a 9b FIG 9a 9b FIG 9a 9b 3 Csatlakoztassa a lapos szalagk belt a berendez s s a kaz nir ny t elektromos panelhoz az 1 k p s az elektromos bra alapj n FIG 10a 10b FIG 10a 10b FIG 10a...

Page 29: ...SET N A villog 77 v szjelz s lland vil g t sa a kaz n haszn lati k zik nyv nek figyelembe v tel vel a k zi visszakapcsol s hat rol termoszt t m k d sbe l p s t jelentheti A m k d sbe l p s h m rs klet...

Page 30: ...klet f t k r MAX Set pontj nak be ll t sa Az alacsony h m rs klet f t k r MAX Set pontj nak be ll t sa Az alacsony h m rs klet f t k r MAX Set pontj nak be ll t sa L pjen a 31 param terbe MAX Set pont...

Page 31: ...at utilizatorul cat si instalatorul de eventualele ac cidente De aceea rugam personalul calificat sa acorde o atentie deosebita conexiunior electrice la finalizarea fiecarei interventii asupra produsu...

Page 32: ...itivului pozitionati intai unitatea Connect AT BT apoi conductele de intrare si iesire ale sistemului si in final cablurile electrice Nivel de protectie electrica IPX4D FIG FIG FIG FIG FIG 4 SCHEMA GE...

Page 33: ...ELIBERAREA POMPELOR DACA ESTE NECESAR ELIBERAREA POMPELOR DACA ESTE NECESAR Daca unitatea a fost inactiva o perioada lunga de timp si unitatile de circulatie sunt blocate desfaceti capacele frontale...

Page 34: ...a punctului de setare MAX pentru incalzire circuit tem Selectarea punctului de setare MAX pentru incalzire circuit tem Selectarea punctului de setare MAX pentru incalzire circuit tem peratura redusa p...

Page 35: ...dhold efter udpakning Alle vore kedler er produceret med omhu for hver enkelt komponent for at undg at forvolde skade p bruger og installat rer Det er meget vigtigt at alle el forbindelser foretages o...

Page 36: ...rbindelserne foretages Elektrisk beskyttelse IPX4D FIG 4 STANDARD INSTALLATION Tegningen viser et eksempel p installation af CONNECT AT BT Bem rk Der skal afs ttes plads til installation af haner medf...

Page 37: ...ller neds ttes i henhold til den beregnede v rdi ndre varme indstilling Korrektionen kan foretages mellem komfort niveauer 5 og 5 INDSTILLING AF ANL GSTEMPERATUR N R VARMEREGULERING IKKE ANVENDES Fixe...

Page 38: ...punkt for det relevante kredsl b KONTROL EFTER INSTALLATION Kontroller anl gstrykket Kontroller der er tilsluttet str m T thedspr v installationen Kontroller at r r og el forbindelser er foretaget ko...

Page 39: ...ja w cianie IPX4D L szeroko 440 mm P g boko 160 mm H wysoko 616 mm Waga netto 16 Kg Maksymalne ci nienie 3 bar Alimentaci n el ctrica 230 10 50 V Hz Potencia m xima consumida por el Connect AT BT 230...

Page 40: ...w r mieszaj cy 11 Puszka po cze elektrycznych 1 Termostato l mite de la instalaci n de baja temperatura con rearme autom tico 2 Termostato l mite de la instalaci n de baja temperatura con rearme manua...

Page 41: ...e powinna przekracza 15 m okablowanie na wyposa eniu ma d ugo 2m CONEXIONES HIDR ULICAS E Impulsi n caldera 3 4 U Retorno caldera 3 4 MD Impulsi n circuito calefacci n 3 4 Mmix Alimentaci n de la inst...

Page 42: ...E INSTALLATION BASSE TEMP RATURE 1 premi re vitesse 2 deuxi me vitesse 3 troisi me vitesse 3A 1A premi re vitesse avec vanne mix ferm e 1A premi re vitesse avec vanne mix ouverte 2A deuxi me vitesse a...

Page 43: ...t gy jt egys geibe 1 Els sebess g 2 M sodik sebess g 3 Harmadik sebess g A VARF REZIDUAL CIRCULATOR SISTEM TEMPERATURA RIDICATA B Capacitate instalatie l h C Varf rezidual m C A D VARF REZIDUAL CIRCUL...

Page 44: ...V MR BL MR BL MR BL NE NE MR BL F2 G V MA RA MMV N Boilers from inside Boilers from outside Boilers from inside boilers from outside Caldaie da interno caldaie da esterno Chaudi res d int rieur chaudi...

Page 45: ...MC MIX cerrado MO MIX abierto NM neutro mix N neutro PBT Bomba B T PAT Bomba A T TLA termostato l mite baja temp rearme autom tico TLM termostato l mite baja temp rearme manual SO sonda SOE sonda exte...

Page 46: ...46...

Page 47: ......

Page 48: ...Cod 10028768 Ed 1 35 06...

Reviews: