Multifunction Control Panel
z
Line Trouble (Line T.)
- The Output will activate for 15 minutes when
telephone-line trouble is detected. If the trouble condition clears, the Output
will restore automatically when the 15 minute interval expires, otherwise, it
will remain active for a further 15 minutes.
z
Reset Fire (Fire res)
- The Output will activate in
Monostable
mode each
a
‘Clear Alarm Memory’
operation is requested (PIN required) at a Keypad
which is assigned to one of the Partitions associated with the Output. If the
Output is programmed as N.C., it can be used as the Negative power supply
to the Fire detectors. In fact, the Negative signal will fail for the programmed
‘Monostable Time’ (refer to Outputs Page) each time a
‘Clear Alarm
Memory’
operation
is requested, thus allowing the Fire detectors to reset.
z
Alarm (Al.r.bel)
- The Output will activate when one of its assigned
Partitions signals Alarm, and will restore when the Alarm cycle ends.
z
Remote Command (Remote)
- The Output will activate when the User executes
a command over the phone (the Control panel Answering device must be enabled).
This signal can be used to activate or stop the OC Output over the phone. The
Output (activated over the phone), can also be restored from the Keypad (via a
‘Clear Alarm Memory’
command). Refer to the User Manual for further details.
z
Negligence (Neglig.)
- The Output will activate when the Control panel
generates a Negligence event, and will restore when the Alarm memory
resets (via a
‘Clear Alarm Memory’
command).
z
Monostable (Monosta.)
- The Output will remain active until the
ON
Time
expires, after which it will be forced to standby for the programmed
OFF Time
.
The following Table shows the restrictions associated with
Outputs with this attribute.
'5
*:&;
9
!
"#
"
$
$
:*:
9
!
%
%!
&
9
:*:
9
' !
'
!
()
(
!*!
%
%+
,
-
#
.
/'-
/'-
If you associate any of the signals in the last section to a ‘
NON Monostable
’
Summary of Contents for KYO 32 M
Page 1: ...0 1 7 167 7 21 0 18 ...
Page 10: ...10 Multifunction Control Panel The NC2 TAST LED Keypad Figure 1 3 The NC2 TAST LED Keypad D D ...
Page 71: ...71 Section 3 Programming from PC 5 11 6 0 1 2 3 1 4 3 3 5 2 3 0 1 2 3 ...
Page 88: ...ISTISBLEUNKYO 2 6 160108 P70 17 6 85 7 6 U O 01 02 5HF FOLQ LQ RU WLRQ ...