Parameter
Description
Aux Acc Time
◼
Sets the acc. time of Main drive (motor) when Aux Motor stops.
⚫
For Follow Lead, Fixed Lag, Network Fbk
◼
The parameter is not used.
AP1-52
Aux Dec Time
⚫
For MMC (Contactor Lag)
◼
It sets the decel time of Main drive (motor) when Aux Motor starts.
⚫
For Follow Lead, Fixed Lag, Network Fbk
◼
The parameter is not used.
AP1-53 / MC2-12
Stage DT
⚫
Sets the delay time to start Lag drive (or AUX motor) when all the conditions for staging are met.
⚫
When the following conditions are met, staging is performed according to priority.
◼
For MMC (Contactor Lag)
◆
The output frequency of Main drive is higher than the next priority AUX’s [Stage Freq].
Example: When the priority order is 1,2,3,4, and 1,2 are operating, the next AUX motor to be
staged is AUX motor 3, and the Main drive’s output frequency has to be higher than AP1-63
(Stage Freq 3).
◆
When PID feedback deviation exceeds the PID reference (setpoint) by AP1-50 (Stage Pres. Dv).
◆
And the above conditions are maintained for the AP1-53 (Stage DT) delay time.
◼
For Follow Lead, Fixed Lag
◆
The output frequency of the Main drive is higher than AP1-61 (Stage freq1).
◆
When PID feedback deviation exceeds the PID reference (setpoint) by AP1-50 (Stage Pres. Dv).
◆
And the above conditions are maintained for the AP1-53 (Stage DT) delay time.
⚫
For Network Fbk
◼
The parameter is not used.
AP1- 54 / MC2-13
Destage DT
⚫
Sets the delay time to stop Lag drive (or AUX motor) when all the conditions for de-staging are met.
⚫
When the following conditions are met, de-staging is performed according to priority.
◼
For MMC (Contactor Lag)
◆
The output frequency of Main drive is less than the next priority AUX’s Destage Freq.
Example: When the priority order is 1,2,3,4 in FILO mode, and 1,2 are operating, the next AUX
motor to be de-staged is AUX motor 2, and the Main drive’s output frequency has to be less
than AP1-71 (Destage Freq 2).
◆
When PID feedback deviation exceeds the PID reference (setpoint) by AP1-59 (Destage Pres).
◆
And the above conditions are maintained for AP1-54 (Destage DT) delay time.
◼
For Follow Lead, Fixed Lag
◆
The output frequency of the Main drive is less than AP1-70 (Destage freq1).
◆
When PID feedback deviation exceeds the PID reference (setpoint) by AP1-59 (Destage Pres).
◆
The above conditions are maintained for AP1-54 (Destage DT) delay time.
⚫
For Network Fbk
◼
The parameter is not used.