Parameter
Description
AP1-89 / MC2-27
Jockey Dly T
⚫
Sets the delay time to stop Jokey pump.
⚫
For MMC (Contactor Lag) and Network Fbk
◼
The parameter is not used.
AP1-90 (Interlock)
Ext. Mtr OL
◼
Yes/No
AP1-91 (Interlock)
Ext. Mtr OL T
⚫
Sets the delay time when exchanging the Main motor.
⚫
For MMC (Contactor Lag), when AP1-55 (Auto Ch Mode) is Main Exchange, the delay time is applied in
the following events.
◼
When the Main motor needs to be changed because an interlock was input for the Main motor.
◼
When the Main motor needs to be changed by the Alternate operation.
⚫
For Follow Lead, Fixed Lag, Network Fbk
◼
The parameter is not used. See
Section 13, Interlock Trip
AP1-94 / MC2-08
* Of Drives
⚫
For Follow Lead, Fixed Lag, Network Fbk
⚫
Sets the number of drives that are actually
operated
by the Lead/Lag system.
◼
Sets the number of drives
operated
in the Lead/Lag system. Compared to AP1-42 (* of Pumps)
which is the number of drives
connected
and can be larger than AP1-94. EX: if AP1-42 is set to “8”
and AP1-94 is set to “5”, only 5 drives are used, and 3 drives are in standby mode. Standby drives
can become part of the alternation sequence.
See
Section 17, Standby
⚫
For MMC (Contactor Lag)
◼
The parameter is not used.
AP1-95 / MC2-28
RunTimeMonitor
⚫
Shows the Pump number corresponding to the (Drive ID) set at COM-01.
◼
For the pump number (Drive ID) displayed, view Run Time parameters AP1-96 (PmpRunTime Day)
and AP1-97 (PmpRunTime Min).
⚫
Lead (+) drive can select all drive ID’s to view Run Time parameters.
⚫
Lag Drives will show their own ID number and cannot select other drive ID’s.
AP1-96 / MC2-29
PmpRunTime Day
⚫
Displays the number of operating days of the pump number (Drive ID) selected in AP1-95
(RunTimeMonitor).
AP1-97 / MC2-30
PmpRunTime Min
⚫
Displays the accumulated operating time (Hr:Min) of the pump number (Drive ID) selected in AP1-95
(RunTimeMonitor).
◼
When the operating time becomes 24:00, it changes to 00:00 and AP1-96 (PmpRunTime Day)
increases by one day.
⚫
NOTE: Parameters AP1-96 and AP1-97 are programmable. The run time can be set for a motor/pump
that has been in operation.
AP1-98 / MC2-31
PmpRunTime Clr
⚫
Resets the time of the selected pump number (Drive ID) in AP1-95. Resets both AP1-96 (PmpRunTime
Day) and AP1-97 (PmpRunTime Min).