7
Application Group 1, AP1 Parameter List
The AP1 Group includes many of the parameters used in the Lead/Lag macro group (MC2). All parameters in the
AP1 Group are listed below. Parameter settings and descriptions are provided in
Section 8, Application Group 1,
Property
Yes / No
Write during operation
X
Write disabled
Parameter
Name
LCD Display
Setting Range
Default
Property*
AP1-00
Jump Code
Jump Code
1
–
99
20
Yes
AP1-20
Soft Fill function options
Soft Fill Sel
0
No
0
No
Yes
1
Yes
AP1-21
Pre- PID
operation frequency
Pre-PID Freq
Low Freq
–
High Freq
30.00
Yes
AP1-22
Pre- PID delay time
Pre-PID Delay
0.0
–
600.0 (sec)
60.0
Yes
AP1-23
Soft Fill escape value
Soft Fill Set
Unit Min
–
Unit Max
20.00
Yes
AP1-24
Soft Fill reference increasing
value
Fill Step Set
0.00
–
Unit Band
2.00
Yes
AP1-25
Soft Fill reference increasing
cycle
Fill Step Time
0
–
9999 (sec)
20
Yes
AP1-26
Soft Fill changing amount
Fill Fdb Diff
0.00
–
Unit Band
0.00
Yes
AP1-30
Flow Comp function options
Flow Comp Sel
0
No
0
No
Yes
1
Yes
AP1-31
Max Comp amount
Max Comp Value
0.00
–
Unit Band
0.00
Yes
AP1-40
1
MMC, Lead-Lag Function
Selection
Lead Lag Sel
0
None
0
None
No
1
Contactor Lag
2
Follow Lead
3
Fixed lag
4
Network Fbk
AP1-41
2
Bypass selection
Regul Bypass
0
No
0
No
No
1
Yes
AP1-42
Number of auxiliary motors
* of Pumps
0 ~ 8
5
No
AP1-43
3
First Priority Motor Number
(Drive ID)
Run Priority
1
–
5
1
No
AP1-44
Display the number of lag
motors in operation
Lag Pump Run
-
-
X
AP1-45
Display priority of motors 1
–
4
Curr. Prty 1
0000
4321
X
AP1-46
Display priority of motors 5
–
8
Curr. Prty 2
0000
0005
X
AP1-47
Lead Lag Operating Status
LeadLag Status
1
Trip
X
2
Manual
3
Interlock
4
Standby
5
Sleep
6
Stop
7
Ready
8
Proc PID
9
Constant
AP1-48
Lag Motor(s) Stop Selection
Lag Stop Sel
0
No
1
Yes
Yes
1
Yes
AP1-49
Alternating Operation
Sequence
ALT Sequence
0
FILO
0
FILO
No
1
FIFO
2
Op time Order
AP1-50
Auxiliary motors staging
pressure difference
Stage Pres. Dv
0
–
PID Unit 100 (%)
5
Yes
AP1-51
Main motor acceleration time
when the number of auxiliary
motors is reduced
Aux Acc Time
0.0
–
600.0 (sec)
2.0
Yes
AP1-52
Main motor acceleration time
when the number of auxiliary
motors is increased
Aux Dec Time
0.0
–
600.0 (sec)
2.0
Yes
AP1-53
Auxiliary motors start delay
time
Stage DT
0.0
–
3600.0 (sec)
5.0
Yes
Summary of Contents for RSi H2P Series