6.3
Control Related Parameters
These parameters have different default settings for Lead/Lag control.
Control Related Parameters - Defaults for Lead Lag
Macro
Parameter
Original
Parameter
LCD Display
Setting Range
Default
Unit
Data
share
NOTES
-
IN-87
DI NC/NO Sel
0 0000 0000
–
1 1111 1111
0 0000 000
1
bit
No
With first bit set to "
1
", Drive is in Run Mode
when Powered Up. P1 terminal input for Fx
(Forward Run) is closed. If using separate
Start/Run command, set first bit back to "0".
0
A Terminal
(NO)
1
B Terminal
(NC)
-
IN-90
DI Status
0 0000 0000
–
1 1111 1111
0 0000 000
1
View
No
Status reflects IN-87 settings.
0
Contact
(Off)
1
Contact
(On)
-
ADV-09
Run
Prevent
0
None
2
Rever
se
Prev
No
Prevent Reverse Rotation.
1
Forward
Prev
2
Reverse
Prev
-
ADV-10
Power- on Run
0
No
1
Yes
No
Related to IN-87.
Yes - Drive will start on Power Up with active
start/run command.
No - Drive requires start/run command after
Power Up.
1
Yes
-
ADV-11
Power- On
Delay
0.0 -6000.0
0.0
secs
No
-
PRT-08
RST Restart
Bit
00
–
11
11
bit
No
Automatic Fault Resets - This is a 2-bit
representation.
00 = Off Off, Disable Auto Fault Resets.
11 = On On, Enable Auto Fault Resets.
Bit 0
Faults other
than LV trip
Bit 1
LV Trip
-
PRT-09
Retry Number
0
–
10
3
-
No
Number of Auto Reset attempts.
-
PRT-10
Retry Delay
0.1
–
600.0 (sec)
5.0
secs
No
Time between Auto Reset attempts.
-
DRV-05
KDP H.O.A Lock
0
Locked
1
Unloc
ked
No
Keypad buttons not locked out.
1
During Run
2
Unlocked
-
OUT-30
Trip OutMode
bit
0000-1111
1
010
-
Any output relay (OUT-31 ~ OUT-
39) that is set to the “Trip”
function will change state with the Interlock function. To
disable the trip output relay for the Interlock function only,
set bit 3 to “0”. (
0
010).
Bit 0
Low voltage
Bit 1
Any faults
other than
low voltage
Bit 2
Automatic
restart final
failure
Bit 3
Operate
with
Interlock
Trip