Macro 2 Group (MC2)
This table lists parameters in the macro group (MC2). It includes the MC2 group parameter number cross referenced
to the original drive parameter along with default settings for Lead/Lag operation. The Notes provide a brief
description of the parameter settings. For detailed descriptions of the parameters, refer to
Group 1, AP1 Parameter Descriptions.
NOTE: For Lag drives only. Parameter MC2-03.
If using a single transducer to the Lead (+) drive only, set Lag drives to Network Feedback. If all drives are receiving
the transducer feedback signal, set Lag drives to same as the Lead (+) drive (Follow Lead or Fixed Lag).
Macro
Parameter
Original
Parameter
LCD Display
Setting Range
Default
Unit
Data
share
NOTES
MC2-01
COM-01
Int485 St ID
1~8
0
-
No
EX: 2 VFD's, VFD#1=1, VFD#2=2, If not changed
from "0", will flash a warning (Int485 ST ID).
MC2-02
PID-01
PID Sel
0:
No
1: Yes
-
No
PID Enabled - default
1:
Yes
MC2-03
AP1-40
Lead-Lag Sel
0:
None
3: Fixed
Lag
-
No
Contactor Lag - MMC Control
Follow Lead - The Lag drive will follow the Main
when called upon to run.
Fixed Lag - The Lag drive will run at a fixed speed
(MC2-15 / AP1-60).
Network Feedback - One Lead (+) drive, all
others Lag
1:
Contactor
Lag
2:
Follow
Lead
3:
Fixed Lag
4:
Network
Fbk
MC2-04
AP1 49
ALT Sequence
0:
FILO
0. FILO
-
Yes
FILO - First In Last Out
FIFO - First In First Out
Op Time - Staging/De-staging based on drive
accumulated operating times.
1:
FIFO
2:
Op Time
Order
MC2-05
AP1-56
Alternate
Time
00:00
–
100:00
24:00
Hr.:Min
Yes
Hr.:Min Set Alternation Time.
MC2-06
AP1-58
Alt Timer Disp
View Only
-
Hr.:Min
No
View accumulated time before alternation
occurs.
MC2-07
AP1-42
* of Pumps
0~8
5
-
Yes
# of pumps/drives connected in Lead/Lag
system. See Standby.
MC2-08
AP1-94
* Of Drives
0~8
5
-
Yes
# of drives running in Lead/Lag system.
MC2-09
DRV-03
Acc Time
0.0~600.0
20
sec
Yes
Acceleration and Deceleration times based on 60
Hz.
MC2-10
DRV-04
Dec Time
0.0~600.0
20
sec
Yes
MC2-11
AP1-50
Stage Pres. Dv
0.00~300.00
5
PSI
Yes
Difference (deviation) between Setpoint and
Feedback to pull in Lag drive. 5 PSI (or more)
below setpoint, Lag drive starts.
MC2-12
AP1-53
Stage DT
0.0~3600.0
5
sec
Yes
Delay time after reaching MC2-11 / AP1-50
MC2-13
AP1-54
Destage DT
0.0~3600.0
5
sec
Yes
Delay time after MC2-14 / AP1-59
MC2-14
AP1-59
Destage Pres.
0.00~300.00
5
PSI
Yes
Difference between Setpoint and Feedback to
drop out Lag drive. 5 PSI (or more) above
setpoint, Lag drive stops.
MC2-15
AP1-60
Lag Freq
Low Freq~ High
Freq
60
Hz
Yes
Fixed Lag frequency setting. Only used when
MC2-03 / AP1-40 is set to Fixed Lag.
MC2-16
AP1- 61
Stage Freq 1
Low Freq~ High
Freq
45
Hz
Yes
Frequency setting of Main drive to pull in Lag
drives. Set lower to pull in sooner. For Follow
Lead and Fixed Lag, only one Staging Freq is used
for all Lags. AP1-62~AP1-68 are not used.
MC2-17
AP1-70
Destage Freq
1
Low Freq~ High
Freq
40
Hz
Yes
Set lower to drop out the Lag drive later. For
Follow Lead and Fixed Lag, only one De-staging
Freq is used for all Lags. AP1-71~AP1-77 are not
used.
MC2-18
AP1-43
Run Priority
View Only
-
-
No
LCD will show priority of running order, middle
digit.
MC2-19
AP1-44
Lag Pump Run
View Only 0~7
0
-
No
This is # of Lag drives (only) running.
MC2-20
AP1-45
Curr. Prty 1
View Only
-
-
No
4321
4 digits representing first 4 drives. If
only 2 drives are used, shows 0021
MC2-21
AP1-46
Curr. Prty 2
View Only
-
-
No
8765
4 more, representing drives 5 ~ 8