Connecting with Other Products
Attribute ID Access
Attribute Name
Range
Definition
1
value changes from FALSE to
TRUE. (Note2)
13
Get
Drive Fault Codes
Refer to the following Drive Fault
Code table (Note2)
15
Get
Control From Net.
0
Commands are made using
sources other than the DeviceNet
communication.
➔
Control is from local
1
Commands are made using the
DeviceNet communication as the
source.
➔
Control is from Network
(Note1) Drive Run Inverter operation using Command
Forward Run Cmd. and Reverse Run Cmd.
Run1
Run1
Trigger Event
Run Type
0
0
Stop
NA
0
→
1
0
Run
Run1
0
0
→
1
Run
Run2
0
→
1
0
→
1
No Action
NA
1
1
No Action
NA
1
→
0
1
Run
Run2
1
1
→
0
Run
Run1
In the table above, Run1 indicates Forward Run Cmd. and Run 2 indicates Reverse
Run Cmd. Commands are made by the EtherNet communication board when the
value changes from 0 (FALSE) to 1 (TRUE). The Forward Run Cmd. value does not
indicate the present operation status of the inverter; it indicates the operation
command value on the EtherNet communication board.
(Note2) Drive Fault
The Drive Fault becomes TRUE when the inverter is faulted.
The Drive Fault Codes for the trips are as follows.
Drive Fault Codes
Fault Code Number
Description
0x0000
None
0x1000
Ethermal
Out Phase Open
InverterOLT
InPhaseOpen
ThermalTrip
UnderLoad
ParaWriteTrip
IOBoardTrip
PrePIDFail
OptionTrip1
OptionTrip2
OptionTrip3
LostCommand
UNDEFINED
LostKeypad