30
890053-03-01
Connecting with Other Products
Service
Service code
Definition
Support for class
Support for
instance
0x0E
Get Attribute Single
No
Yes
0x10
Set Attribute Single
No
Yes
③
Control Supervisor Objects (Class 0x29, Instance 1)
Attribute
Attribute ID Access
Attribute Name
Range
Definition
3
Get/Set Forward Run Cmd.
0
Stopped
Forward run (Note1)
1
4
Get/Set
Reverse Run
Cmd.
0
Stopped
Reverse run (Note1)
1
5
N/A
Net Control
-
Configurable only with the inverter
parameter.
6
Get
Drive State
0
Vendor Specific
1
Startup
2
Not Ready (resetting in progress)
3
Ready (stopping in progress)
4
Enabled (running, not applicable to
deceleration stop)
5
Stopping (decelerating)
6
Fault Stop
7
Faulted (trip occurred)
7
Get
Running Forward
0
Drive stopped.
1
Running Forward
8
Get
Running Reverse
0
Drive stopped.
1
Running Reverse
9
Get
Drive Ready
0
Resetting in progress or trip
occurred
1
Inverter is ready for operation
10
Get
Drive Fault
0
Trip has not occurred
1
Trip has occurred
12
Get/Set
Drive Fault Reset
0
Trip reset to release the trip.
Resetting will begin only when the