25
EN
8.3) TESTING
- Check that the safety devices work correctly.
- Check the opening/closing forces at the points set out in EN 12445 with an appropriate instrument.
- If the forces are greater, install a safety device compliant with EN12978 (e.g. safety sensitive edge) and repeat the measurements.
- Check the correct setup of the operation logic and that the manual release works properly.
8.4) PARAMETERS, LOGICS AND SPECIAL FUNCTIONS
The following tables describe the functions available on the control unit.
8.4.1) PARAMETERS (
PAR
)
MENU
FUNCTION
MIN-MAX-(Default)
MEMO
TCA
Automatic closing time. Enabled only with logic “TCA”=ON.
At the end of the set time, the control unit commands a closing maneuver .
3-240-(40)
tped
The passage left open by the gate leaf during the partial opening (pedestrian) is adjusted.
10-99-(50)
fsto
The opening speed is adjusted.
50-99-(99)
fstc
The closing speed is adjusted.
50-99-(99)
sldo
Adjusts the slowdown speed of sliding door during the opening phase* (Fig.10 -slow Open).
10-50-(25)
sldc
Adjusts the slowdown speed of sliding door during the closing phase * (Fig.11 -slow Close).
10-50-(25)
tsmo
Sets the starting point of the slowdown during the opening phase (Fig.10- beginning of the slow
Open). The value is expressed in percentage on the entire stroke.
1-99-(20)
tsmc
Sets the starting point of the slowdown during the closing phase (Fig.11- beginning of the slow
Close). The value is expressed in percentage on the entire stroke.
1-99-(20)
PMO
Adjusts the motor torque applied to sliding door during the opening phase.*
1-99-(20)
PMC
Adjusts the motor torque applied to sliding door during the closing phase.*
1-99-(20)
PSO
Adjusts the motor torque applied to sliding door during the slowdown in opening phase * (Fig.9
- Slow Open).
1-99-(20)
PSC
Adjusts the motor torque applied to sliding door during the slowdown in closing phase * (Fig.10
- Slow Close).
1-99-(20)
tls
Activation time of the courtesy light contact. Value expressed in seconds. At the beginning of
each maneuver the contact latches for the set time. See the description of AUX1 parameter.
1-240 (60)
aux1
It selects the operating mode of the AUX 1 output:
0: Open gate indicator light. The light is off when the door is closed, flashes with moving door
and is on with open door. See wire diagram.
1: Second radio channel. The output is controlled by the radio channel of the built-in receiver
(see RADIO Menu).
2: Service light. The contact closes for the time preset with TLS parameter. The countdown
starts at the inception of operation.
3: Photo-test Used to power the photocell transmitters in TEST mode
See wiring diagram Fig.23.
0-3-(1)
aux2
Same operation features as AUX1 output, but referred to terminals AUX2.
ATTENTION!: Max AUX2 output voltage is 24Vdc/0,5 A Max. You can directly power 24Vdc
devices, as shown in Fig. 24.
0-3-(0)
* ATTENTION: A WRONG SETTING OF THESE PARAMETERS CAN BE DANGEROUS.
RESPECT THE REGULATION IN FORCE!
Measure that impact forces comply with the values laid down in regulation en 12445. change, if necessary, the operating parameters and repeat the
measurements. Once you have manually modified the parameters sldo, sldc, pmo, pmc, pso, psc, the controller performs a complete manoeuvre to
learn the new parameters.
8.4.2) LOGICS (
LOG
)
MENU
FUNZIONE
ON-OFF-(Default)
MEMO
TCA
Enables or disables automatic closing
On: automatic closing enabled
Off: automatic closing disabled
(ON)
IbL
Enables or disables condominium function.
On: condominium function enabled. The step-by-step impulse or transmitter impulse has no
effect during the opening phase.
Off: condominium function disabled.
(OFF)
ibca
The multi-flat function is enabled or disabled during the TCA counting.
On: the bloc of flat function is enabled. The Step-by-Step signal or the transmitter signal has no
effect during the TCA counting.
Off: the bloc of flat function is disabled.
(OFF)
SCL
The rapid closure is enabled or disabled
On: rapid closure is enabled. When the gate is open or moving, the photocell activation causes
the automatic closure of the gate after 3 s. It is activated only with
TCA
:ON
Off: rapid closure is disabled.
(OFF)
Summary of Contents for BULL 1224 TURBO
Page 2: ...2 A B 1 200 245 316 400 300 215 400 34mm BULL PI Optional 40 3 1 8 2 0 4 7 0 1 8 0 2 3...
Page 3: ...3 V Z R 4 7 B F T MIN 10 mm MAX 20 mm MIN 120 mm MAX 140 mm 5 6 R D R D...
Page 5: ...5 12 13 14 C L 7 4 1 2 3 POWER 2 x 1 5 RG 58 5 4 x 0 25 4 6 5 2 x 0 25 3 x 0 25 15...
Page 7: ...7 18 19 A B C...
Page 75: ...75...