Modbus Register Map
63
PEM533_D00013_00_M_XXEN/06.2015
Table 8.6: Minimum values per demand period
8.6 Peak demand
The value of the peak demand register is the actual value x 1,000, that means, to ob-
tain a value in kW, kVA or kvar, the value of the register has to be divided by 1000.
8.6.1 Peak demand this month
Table 8.7: Peak demand of this month
1654
RO
λ
ges min
INT32
x1000
1656
RO
f
min
INT32
x100, Hz
1658
RO
min. voltage unbalance
INT32
x1000
1660
RO
min. current unbalance
INT32
x1000
1662
RO
THD
UL1 min
INT32
x10.000
1664
RO
THD
UL2 min
INT32
x10.000
1666
RO
THD
UL3 min
INT32
x10,000
1668
RO
THD
I1 min
INT32
x10,000
1670
RO
THD
I2 min
INT32
x10,000
1672
RO
THD
I3 min
INT32
x10,000
Register
Prope
rty
Description Format
1800…1804
RO
Peak demand
P
of this month
x1000, kW
1805…1809
RO
Peak demand
Q of this month
x1000, kvar
1810…1814
RO
Peak demand
S
of this month
x1000, kVA
1815…1819
RO
Peak demand
I
1
of this month
x1000, A
1820…1824
RO
Peak demand
I
2
of this month
x1000, A
1825…1829
RO
Peak demand
I
3
of this month
x1000, A
Register
Property
Description Format
Unit
Summary of Contents for PEM533