Modbus Register Map
53
PEM533_D00013_00_M_XXEN/06.2015
8. Modbus Register Map
This chapter provides a complete description of the Modbus register (protocol ver-
sion 6.0) for the PEM533 series to facilitate access to information. In general, the
registers are implemented as Modbus Read Only Registers (RO = read only) with
the exception of the DO control registers, which are implemented as Write Only
Registers (WO = write only).
PEM533 supports the 6-digit addressing scheme and the following Modbus func-
tions:
1. Holding register for reading values
(Read Holding Register; function code 0x03)
2. Register for setting the DO status
(Force Single Coil; function code 0x05)
3. Register for device programming
(Preset Multiple Registers; function code 0x10)
For a complete Modbus protocol specification, visit
http://www.modbus.org.
8.1 Basic measurements
Register
Property Description
Format
Scale/
unit
0000
RO
U
L1
1)
UINT32
×100, V
2)
0002
RO
U
L2
1)
UINT32
×100, V
0004
RO
U
L3
1)
UINT32
×100, V
0006
RO
Ø
U
LN
UINT32
×100, V
0008
RO
U
L1L2
UINT32
×100, V
0010
RO
U
L2L3
UINT32
×100, V
0012
RO
U
L3L1
UINT32
×100, V
0014
RO
Ø
U
LL
UINT32
×100, V
0016
RO
I1
UINT32
×1000, A
0018
RO
I2
UINT32
×1000, A
0020
RO
I3
UINT32
×1000, A
0022
RO
Ø
I
UINT32
×1000, A
Summary of Contents for PEM533
Page 24: ...Installation and connection 24 PEM533_D00013_00_M_XXEN 06 2015...
Page 86: ...Modbus Register Map 86 PEM533_D00013_00_M_XXEN 06 2015...
Page 90: ...Technical data 90 PEM533_D00013_00_M_XXEN 06 2015...
Page 93: ...INDEX 93 PEM533_D00013_00_M_XXEN 06 2015...
Page 94: ......
Page 95: ......