Operation
40
PEM533_D00013_00_M_XXEN/06.2015
6.9 Setup: possibilities
The table shows the messages indicated on the display, their meaning and the set-
ting possibilities.
Display entry
Level 1
Level 2
Parameters
Description
Setting options
Factory
setting
PROGRAM-
MING
Setup mode
PASWORD
Password
Enter password
/
0
PAS SET
Change password?
YES/NO
NO
NEW PAS New password
Enter new password 0000…9999
0
SYS SET
System settings
YES/NO
NO
Type
Type of connec-
tion
Select type of con-
nection
WYE/DELTA/
DEMO
WYE
PT
Voltage trans-
former
Select transformer
ratio for the voltage
transformer
1…2200
1
CT
Measuring cur-
rent transformers
Select CT trans-
former ratio
1…30,000 (1 A)
1… 6,000 (5 A)
1
PF SET Power factor rule
Power factor rule
*
IEC/IEEE/-IEEE
IEC
KVA SET
S
calculation
method **
V/S
V
I1 REV I
1
CT
I
1
Change CT polar-
ity
YES/NO
NO
I2 REV I
2
CT
I2
Change CT polar-
ity
YES/NO
NO
I3 REV I3 CT
I
3
Change CT polar-
ity
YES/NO
NO
COM 1 SET
Configure communications interface
YES/NO
NO
ID
Address for
measuring
device
Set address for
measuring device
1-247
100
Baud Baud rate
Set baud rate
1200/2400/4800/
9600/19200 bps
9600
CONFIG Parity bit
Configuration
Parity bit
8N2/8O1/8E1/
8N1/8O2/8E2
8E1
Summary of Contents for PEM533
Page 24: ...Installation and connection 24 PEM533_D00013_00_M_XXEN 06 2015...
Page 86: ...Modbus Register Map 86 PEM533_D00013_00_M_XXEN 06 2015...
Page 90: ...Technical data 90 PEM533_D00013_00_M_XXEN 06 2015...
Page 93: ...INDEX 93 PEM533_D00013_00_M_XXEN 06 2015...
Page 94: ......
Page 95: ......