Installation and connection
23
PEM533_D00013_00_M_XXEN/06.2015
4.8 Digital inputs
The universal measuring device PEM533 provides 6 digital inputs. The inputs are
supplied by a galvanically isolated DC 24 V voltage. Through an external wiring a
current of at least
I
min
> 2.4 mA must flow in order to trigger the inputs.
4.9 Digital outputs
The universal measuring device PEM533 features 2 configurable outputs
(N/O contact).
Rated operational
voltage
AC 230 V
DC 24 V
AC 110 V
DC 12 V
Rated operational
current
5 A
5 A
6 A
5 A
DI1
DIC
DI5
DI6
DI2
DI3
DI4
DO13
DO14
DO23
DO24