Table 8.2: Bit sequence alarm register (0082)
6)
The SOE pointer points to the last entry added. The event log can store up to 64 events. It
works like a ring buffer according to the FIFO principle: The 65
rd
value overwrites the first
value, the 66
th
the second one and so on. The event log can be reset in the setup parameter
menu (see page 42).
8.2 Energy measurement
Table 8.3: Energy measurements
Note: After reaching the maximum value of 999.999.999 kWh/kvarh/kVAh, the measure-
ment starts again with 0.
Bit in register 0082
Alarm event
B0…B2
Reserved
B3
Setpoint 1
B4
Setpoint 2
B5
Setpoint 3
B6
Setpoint 4
B7
Setpoint 5
B8
Setpoint 6
B9
Setpoint 7
B10
Setpoint 8
B11
Setpoint 9
all other bits
Reserved
Register Property
Description
Format
Unit
0200
RW
Active energy import
UINT32
kWh
0202
RW
Active energy export
UINT32
kWh
0204
RO
Active energy net amount
INT32
kWh
0206
RO
Total active energy
UINT32
kWh
0208
RW
Reactive energy import
UINT32
kvarh
0210
RW
Reactive energy export
UINT32
kvarh
0212
RO
Reactive energy net amount INT32
kvarh
0214
RO
Total reactive energy
UINT32
kvarh
0216
RW
Apparent energy
UINT32
kVAh
Summary of Contents for PEM533
Page 24: ...Installation and connection 24 PEM533_D00013_00_M_XXEN 06 2015...
Page 86: ...Modbus Register Map 86 PEM533_D00013_00_M_XXEN 06 2015...
Page 90: ...Technical data 90 PEM533_D00013_00_M_XXEN 06 2015...
Page 93: ...INDEX 93 PEM533_D00013_00_M_XXEN 06 2015...
Page 94: ......
Page 95: ......