Tests, service, troubleshooting
69
CMS460-D_D00045_01_M_XXEN/07.2016
7.3.2
Device error display (channel-related)
LED "ALARM 1“ lights up. The programmed common alarm relay switches. The
following test is shown on the display of the CMS460-D:
Line 1:
FAULT, Alarm 1 of 1 pending alarms
Line 2:
Alarm status and alarm text
No alarm
Prewarning
Alarm, fault
Line 3:
Error code (see „Device error display“ on page 67)
Line 4:
BMS bus address of the CMS460-D and measuring channel
on which the alarm has occurred.
Possible causes:
Incorrect basic programming of the CMS460-D.
Wrong p.c.b. assembly at four channels in succession.
Internal memory fault.
Faulty channels after test.
The device errors remain saved until the "RESET“ button is pressed. An entry is
made in the history memory with the suffix "device error".
If a device error continues to exist after a RESET, the CMS460 has to be re-
placed.
7.3.3
External alarm
LED "ALARM 2“ lights up. The programmed common alarm relay switches.
Possible causes:
Alarm message from an external device
Device failure
Fault 1/1
Device error
11
Addr.: 2 Channel: 4
(
*
)
(
Summary of Contents for LANTRAXX CMS460-D
Page 6: ......
Page 21: ...Installation and connection 21 CMS460 D_D00045_01_M_XXEN 07 2016 4 3 2 Wiring diagram ...
Page 26: ...Installation and connection 26 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 28: ...Installation and connection 28 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 66: ...Operation 66 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 70: ...Tests service troubleshooting 70 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 85: ......
Page 86: ......
Page 87: ......