1.Factor (for PRESET)
Set the multiplication factor for the latest measured value. Setting range:
1…99 %, resolution of setting 1 %.
Recommended setting (factory setting): Factor 3
2.Offset (for PRESET)
Set the offset value that is to be added to the product of the "current meas-
ured value x factor". Setting range: 0…20 A, resolution of setting:
Setting range
Resolution of setting
0…20 mA
1 mA
25…50 mA
5 mA
60…200 mA
10 mA
250…500 mA
50 mA
600 mA… 2 A
100 mA
2.5 A…5 A
0.5 A
6 A…20 A
1.0 A
Recommended setting (factory setting): Offset 30 mA
3.PRESET
Make sure that all existing insulation faults are eliminated before using the
preset function!
Presetting is carried out for all measuring channels on this device.
Exceptions:
If a channel is disabled the response value will not be changed.
When the current measured value is 0 mA, the smallest possible
response value is set: Type A measuring current transformer : 100 mA
Exit
1.Factor:
*3
2.Offset:
30 mA
3.PRESET
Summary of Contents for LANTRAXX CMS460-D
Page 6: ......
Page 21: ...Installation and connection 21 CMS460 D_D00045_01_M_XXEN 07 2016 4 3 2 Wiring diagram ...
Page 26: ...Installation and connection 26 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 28: ...Installation and connection 28 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 66: ...Operation 66 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 70: ...Tests service troubleshooting 70 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 85: ......
Page 86: ......
Page 87: ......