Operation
32
CMS460-D_D00045_01_M_XXEN/07.2016
6.2
Working in operating mode
6.2.1
Standard display
In the operating mode, the CMS460-D displays a bar graph which shows what
percentage of the of the set response value
I
n2
(alarm) and
I
n1
(prewarning)
has been reached for each of the 12 measuring channels. .
6.2.2
Alarm causes
Possible causes of alarm messages:
The value falls below or exceeds the set response value or the prewarn-
ing threshold during current or residual current measurement.
Fault measuring current transformer or measuring current transformer
connection.
Device error (see „Device error display“ on page 67)
The indication in the display is dependent on the set response
value:
Response value
Indication 0 mA
10 mA…2 A
for measured values ≤ 10 mA;
2…20 A
for measured values ≤ 0.5 % of the
response value
100%
50%
k 1 2 3 4 5 6 7 8 9 10 11 12
0%
Channel disabled
Channel enabled
Channel enabled,
current is flowing.
(height
≥
2 graduation
(height = 1 graduation