Operation
39
CMS460-D_D00045_01_M_XXEN/07.2016
6.3.3
Main menu functions
Menu item
Function
Page
Exit Exit
menu
mode
-
1.Alarm/
meas.values
Displays the following for each measuring
channel, if applicable: Prewarning, alarm,
measured value, response value, channel disa-
bled.
2.% Bar graph
The percentage of the total set alarm value
I
n2
(alarm) and
I
n1
(prewarning) which has been
reached by each of the 12 measuring channels
is indicated.
3.History
Displays the history (300 data records) with
information about messages, acknowledge-
ments and associated times. Displays the mini-
mum and maximum overcurrent and the
associated address and channel after the
occurrence of an alarm.
4.Harmonics
Displays the following for the selected measur-
ing channel: Measured value, THF (Total Har-
monic Factor), DC component, fundamental
component and harmonics in mA.
5. Data logger
Displays the recorded measured values (300
data records/channel) for each measuring
channel.
6.Settings
Settings for this CMS460-D are made here.
7.Control
This menu offers various control options, such
as TEST, RESET, Test communication.
Summary of Contents for LANTRAXX CMS460-D
Page 6: ......
Page 21: ...Installation and connection 21 CMS460 D_D00045_01_M_XXEN 07 2016 4 3 2 Wiring diagram ...
Page 26: ...Installation and connection 26 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 28: ...Installation and connection 28 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 66: ...Operation 66 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 70: ...Tests service troubleshooting 70 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 85: ......
Page 86: ......
Page 87: ......