Operation
54
CMS460-D_D00045_01_M_XXEN/07.2016
60…200 s
10 s
250…500 s
50 s
600…999 s
100 (99) s
6.Cut-off frequency
Set the characteristics for the frequency response of load current measure-
ment
I
n
and current measurement
I
.
The frequency response of the equipment can be set for a linear frequency re-
sponse (up to the maximum frequency of 2000 Hz) if used for fire protection
or for a frequency response in accordance with IEC 60990 for personnel pro-
tection. For plant protection, the residual current is measured up to the rated
system frequency. The figure below shows the corresponding frequency re-
sponse.
Param.
Objective
50 Hz
Plant protection: Only evaluates the fundamental compo-
nent of the current measurement.
60 Hz
Plant protection: Only evaluates the fundamental compo-
nent of the current measurement.
IEC
Frequency response acc. to IEC 60990: Above 200 Hz
(approx.), the set response value increases according to the
hazard curve in IEC 60990.
None
Fire protection: Response factor remains the same over the
entire frequency range.
Summary of Contents for LANTRAXX CMS460-D
Page 6: ......
Page 21: ...Installation and connection 21 CMS460 D_D00045_01_M_XXEN 07 2016 4 3 2 Wiring diagram ...
Page 26: ...Installation and connection 26 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 28: ...Installation and connection 28 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 66: ...Operation 66 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 70: ...Tests service troubleshooting 70 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 85: ......
Page 86: ......
Page 87: ......