The user interface of the internal Web server
38
6.6.6
Data logger setting
This submenu can be used to configure up to 20 data loggers. The loggers are assigned ac-
cording to the channels and BMS address. The BMS data are recorded depending on the pre-
set percentage modification of a measuring value. It must also be specified whether the
oldest data record is to be overwritten in case of a full memory. In addition, the whole stor-
age of the logger can be deleted.
For data logger configuration, enter the following parameters into the respective edit fields:
1. The BMS device address of the device to be monitored (1 to 150);
2. The BMS channel of the previously addressed device (1 to 12);
3. The percentage measuring value above which the measuring value is to be recorded. The possible
value range is 0 to 90 %;
4. Select "Yes" or "No" from the drop-down menu to overwrite the oldest data record;
5. Click "Clear memory" if you have decided to delete the previously recorded data records.
6. Confirm your actions with the button "Save" or stop your actions with "Cancel".“
6.6.7
History memory setting
Here you have the possibility to delete history data completely.
6.6.8
System logger setting
Here, you can delete the system logger completely.