Application of the internal OPC server
64
8.3.2
Data collection of the whole BMS system via BMS addresses and channels
1. Double-click the server icon or click the "Bender OPC Server" writing (under Data Access V2). A basic
structure will appear in the frame on the left.
2. In the right frame click the "DA Browse“ tab. The name of the OPC server and its IP address will
appear on the highest level. Then click the plus sign next to it , the available addresses 5 and 1 in the
BMS system will be displayed.
3. Click the plus sign next to BMS address 5, all channels of the respective device will appear. Then click
the on the plus signs of the channels 2 and 4. The OPC data structure (items) where the BMS measur-
ing values are collected will appear. In this example, the items: value, type and alarm will be dis-
played.