![Bender FTC470XET Operating Manual Download Page 75](http://html1.mh-extra.com/html/bender/ftc470xet/ftc470xet_operating-manual_2731753075.webp)
75
11. Technical data
11.1 Data in tabular form
Insulation coordination acc. to IEC 60664-1
Rated insulation voltage........................................................................................................................................ AC 250 V
Rated impulse voltage/pollution degree.................................................................................................................. 4 kV/3
Voltage ranges
Supply voltage U
s
(see nameplate) ........................................................................................................ AC/DC 85...276 V
.................................................................................................................................................. DC independent of polarity
Frequency range U
s
.......................................................................................................................................... 50...400 Hz
Power consumption ................................................................................................................................................
≤
12 VA
Displays
Ethernet ..................................................... 2 LEDs: LINK (Ethernet connection set up), ACT (TCP/IP connection active)
BMS bus .............................................................................................................................................. 2 LEDs: BMS, FAULT
Device/ Web server ................................................................................................................................. 1 Power ON LED:
Interfaces
Ethernet:
Interface/ protocol............................................................................................................ RJ45 socket, Ethernet 10Base-T
Cable length...........................................................................................................................................................
≤
100 m
Recommended cable ............................................................... screened network cable with RJ45 plug, STP, category 6
Baud rate ......................................................................................................................................... 10 MBit/s, half duplex
IP addressing ....................................................................................................................................... setting per browser
IP address, factory setting ............................................................................................................................ 192.168.0.254
Net mask, factory setting ............................................................................................................................ 255.255.255.0
BMS bus:
Interface/ protocol............................................................................................... RS-485 (terminals A/B) / BMS protocol
Baud rate............................................................................................................................................................... 9.6 kBit/s
Max. cable length .................................................................................................................................................. 1200 m
Recommended cable (screened, screen on one side connected to PE) ................................................... J-Y(St)Y 2 x 0.6
Terminating resistor ................................................................................................. terminal connection, 120
Ω
(0.5 W)
Device address / factory setting.................................................................................................. per DIP switch, 1...30 / 1
OPC via Ethernet:
OPC data access ........................................................................................................................................................... v 2.0
ProgID .......................................................................................................................... Bender.OPC.Server.FTC470XET.DA
System configuration
of the FTC Web server, of the BMS devices connected to the FTC:
Password, factory setting................................................................................................................................................ ftc
General data
EMC immunity ............................................................................................................................................. EN 61000-6-2
EMC emissions ............................................................................................................................................. EN 61000-6-4
Shock resistance acc. to IEC 60068-2-27 (device in operation) ...................................................................... 15 g/11 ms
Bumping IEC 60068-2-29 (during transport) .................................................................................................... 40 g/6 ms
Vibration resistance IEC 60068-2-6 (during operation) ..........................................................................1 g / 10...150 Hz
Vibration resistance IEC 60068-2-6 (during transport) ......................................................................... 2 g / 10 ... 150 Hz
Ambient temperature, during operation................................................................................................... -10 °C...+55 °C
Storage temperature range -40 °C...+70 °C
Climatic class acc. to DIN IEC 6072160721-3-3 ............................................................................................................3K5
Summary of Contents for FTC470XET
Page 10: ...Safety instructions 10 TGH1375en 02 2010...
Page 18: ...The FTC470XET protocol converter 18 TGH1375en 02 2010...
Page 56: ...Web server application examples 56 TGH1375en 02 2010...
Page 78: ...Technical data 78 TGH1375en 02 2010...
Page 80: ...Frequently asked questions 80 TGH1375en 02 2010...