Installation MACH1000
Release 07 08/2022
57
IEEE C37.90.1
Damped oscillation
DC Power Line
±2,5 kV line/earth; ±1 kV line/line
AC Power Line
±2,5 kV line/earth; ±1 kV line/line
Data line
±2,5 kV line/earth; ±1 kV line/line
IEEE C37.90
H.V. Impulse
DC Power Line
± 5 kV line/earth
AC Power Line
± 5 kV line/earth
IEEE C37.90
dielectric strength
DC Power Line power supply
unit characteristic value C, L
500 V AC
AC Power Line power supply
unit characteristic value G, M
2000 V AC
DC Power Line power supply
unit characteristic value G, M
2000 V AC
Signal contact characteristic
value C, L, G, M
2000 V AC
EMC interference emission
EN 55032
Class A
FCC 47 CFR Part 15 Class A
German Lloyd
Classifi Construction Guidelines VI-7-3 Part 1 Ed. 2001
Environment TYPE
test, test according
to
Description
Test level
IEC 60068-2-1
Cold
−
40 °F (
−
40 °C), 16 hours
IEC 60068-2-2
Dry heat
+185 °F (+85 °C), 16 hours
IEC 60068-2-30
Relative humidity
95 % (non condensing)
131 °F (55 °C), 4 cycles
IEC 60068-2-6
Vibration, test Fc
2 - 9 Hz with 3 mm amplitude
1 g at 9 - 150 Hz
1.5 g at 200 - 500 Hz
IEC 60068-2-27
Shock, test Ea
15 g at 11 ms
EMC interference
immunity
IEEE 1613 EMI TYPE
test, test according to
Description
Test level