56
Installation MACH1000
Release 07 08/2022
EMC and immunity
EMC interference
immunity
IEC/EN 61850-3 EMI
TYPE test, test
according to
Description
Test level
IEC/EN 61000-4-2
Electrostatic discharge
Contact discharge
±8 kV
Air discharge
±15 kV
IEC/EN 61000-4-3
Electromagnetic field
80 MHz ... 2700 MHz
20 V/m
IEC/EN 61000-4-4
Fast transients (burst)
DC Power Line
±4 kV
AC Power Line
±4 kV
Data line
±4 kV
IEC/EN 61000-4-5
Voltage surges
DC Power Line
±2 kV line/ground; ±1 kV line/line
AC Power Line
±4 kV line/ground; ±2 kV line/line
Data line
±4 kV line/ground
IEC/EN 61000-4-6
Conducted disturbances
150 kHz ... 80 MHz
10 V
IEC/EN 61000-4-12
Damped oscillation
DC Power Line
±2,5 kV line/earth; ±1 kV line/line
AC Power Line
±2,5 kV line/earth; ±1 kV line/line
Data line
±2,5 kV line/earth; ±1 kV line/line
IEC 60255-5
dielectric strength
DC Power Line power supply
unit characteristic value C, L
500 V AC
AC Power Line power supply
unit characteristic value G, M
2000 V AC
DC Power Line power supply
unit characteristic value G, M
2000 V AC
Signal contact characteristic
value C, L, G, M
2000 V AC
EMC interference
immunity
IEEE 1613 EMI TYPE
test, test according to
Description
Test level
IEEE C37.90.3
Electrostatic discharge
Contact discharge
±8 kV
Air discharge
±15 kV
IEEE C37.90.2
Electromagnetic field
80 MHz ... 1000 MHz
35 V/m (peak)
IEEE C37.90.1
Fast transients (burst)
DC Power Line
±4 kV
AC Power Line
±4 kV
Data line
±4 kV
Summary of Contents for Hirschmann MACH1000 Series
Page 67: ...Installation MACH1000 Release 07 08 2022 67 ...
Page 68: ......