background image

15

When the required number of linearising break-
point has been entered, return to the linearisation
sub-menu by pressing 

E

.  

The indicator will display

the 'Add' or 'dEL' prompt depending upon the last
sub-function used.  The indicator input current and
corresponding indicator display at each break-
point, which is the segment finishing point as
shown in Fig 8, can now be entered using the ‘in’
and ‘diSP’ sub-functions.

Using the 

 or 

 button select 'in' from the sub-

menu and press 

P

 which will reveal the starting

point for the first segment '0 : n', where n is the
total number of break-point entered. Press 

P

 and

use the 

 and 

 buttons and the 

P

 button to

move between digits, to enter the input current at
which the first break-point is required, usually
4.000mA.   When set as required, press 

E

 to return

to the ‘0  :  n’ prompt from which the the next
break-point can be selected using the 

 and 

buttons.  When the required break-point has been
selected press 

P

 and enter the indicator input

current at this break-point. Repeat this procedure
until the indicator input current at all the the break-
points has been defined and then return to the ‘in’
sub-function by pressing the 

E

 button.

The corresponding indicator display at each of the
break-points can now be defined using the ‘diSP’
sub-function    Using the 

 and 

 buttons select

the ‘diSP’ sub-function and press 

P

 which will

reveal the starting point for the first break-point
'0 : n', where n is the total number of break-points
entered. Press 

P

 and use the 

 and 

 buttons

and the 

P

 button to move between digits, to enter

the required indicator display at the first break-
point.  When set as required, press 

E

 to return to

the ‘0  :  n’ prompt from which the the next break-
point can be selected using the 

 or 

 buttons.

When the required break-point has been selected
press 

P

 and set the required indicator display at

this break-point.

Repeat this procedure until the indicator display at
all the break-points has been defined and then
return to the ‘SEt’ function in the configuration
menu by pressing the 

E

 button twice.

6.3  Lineariser error message

If an attempt is made to position a break-point at a
current which is not greater than the current of the
preceeding break-point, or at a current which is not
less than the current of the following break-point,
the error message ‘FaiL’ will be displayed.  This
error message will also be displayed if an attempt
is made to position a  break-point outside the
current range 3.8 to 21.0mA.

6.4 Under and over-range

The lineariser does not change the under and
over-range indication described in section 6.12.
At input currents below that specified for the first
break-point (0), the indicator will continue to use
the specified slope of the first segment.  Although
not guaranteed, most indicators will continue to
function normally with an input current between
1.8mA and 4mA, at lower currents the instrument
will display ‘LPLo’ before it stops functioning.

At input currents above that specified for the last
break-point, the indicator will continue to use the
slope specified for the last lineariser segment.

6.5  Lineariser default configuration

When the lineariser is reset to the default
conditions using the ‘rSEt’ reset function described
in section 6.11, the defaults conditions are:

BA504E  BA524E

First break-point 4mA

     0.0

  0.00

Second break-point 20mA

100.0

100.00

Summary of Contents for BA504E

Page 1: ...Issue 2 14th December 2011 BA504E BA524E General Purpose loop powered field mounting indicators Issue 2...

Page 2: ...ver range 6 5 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Custom...

Page 3: ...e g temperature flow pressure or level The BA504E and BA524E are not certified for use in explosive atmospheres For hazardous area application the BA304E BA304NE BA324E or the BA324NE should be used 2...

Page 4: ...indicator and the ACSP access setpoints in display mode function has been enabled P E Provides access to the configuration menu via optional security code Note BA524E only If the indicator has been c...

Page 5: ...ally joined and may be used for linking cable screens The indicator s earth terminal is connected to the carbon loaded GRP enclosure If this enclosure is not bolted to an earthed post or structure the...

Page 6: ...EMC Both instruments compy with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs with the screens connected at one poin...

Page 7: ...tion Default Configuration BA504E BA524E Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph...

Page 8: ...8...

Page 9: ...n 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or pre...

Page 10: ...etween the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the...

Page 11: ...n and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit secur...

Page 12: ...r volumetric units by filling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break point required should f...

Page 13: ...13...

Page 14: ...dd a break point Adds a new break point before the displayed break point The calibration of existing break points is not changed but the identification number of all subsequent break point is increase...

Page 15: ...tor display at the first break point When set as required press E to return to the 0 n prompt from which the the next break point can be selected using the or buttons When the required break point has...

Page 16: ...If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop w...

Page 17: ...n Both indicators can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9...

Page 18: ...polarised and current will only flow in one direction Ron less than 5 0 7V Roff greater than 1M Fig 10 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switc...

Page 19: ...19...

Page 20: ...setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function as High or Low See section 8 3 5 no nC Normally open or...

Page 21: ...r fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 22: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 23: ...int plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 14 Fig 14 Displayed value and setpoints on bargra...

Page 24: ...cting it in series with the indicator s 4 20mA input as shown in Fig 16 which increases the maximum indicator voltage drop from 1 2 to 5V Fig 16 Loop powered backlight Providing the increased voltage...

Page 25: ...l pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel b...

Reviews: