background image

22

8.3.9  Alarm silence time:   SiL

This function is primarily intended for use in small
installations where the alarm output directly
operates an alarm annunciator such as a sounder
or beacon.  When the alarm silence time, which is
adjustable between 0 and 3600 seconds in 1
second increments, is set to any figure other than
zero, the 

P

 push-button becomes an alarm accept

button.   After an alarm has occurred, operating the

P

 button will cause the alarm output to revert to the

non-alarm condition for the programmed alarm
silence time.  If the alarm condition still exists at
the end of the silence time, the alarm output will be
reactivated.  During the silence time the indicator
alarm annunciator will flash until the silence time
expires or the alarm is cleared.

If the ‘FLSH’ function, which flashes the indicator
display when an alarm occurs has been enabled,
it will only function when the alarm output is
activated, not during the silence time.  See section
8.3.11

To adjust the alarm silence time select 'SiL' from
the alarm configuration menu and press 

P

 which

will reveal the existing silence time.  The flashing
digit of the silence time can be adjusted using the

 and 

 push-buttons, and the 

P

 button to move

control to the other digits.  When the required
silence time has been entered press 

E

 

to return to

the alarm menu.

8.3.10 Flash display when alarm occurs

 

‘FLSH’

In addition to the two alarm annunciators on the
top left hand corner of the indicator display which
show the status of both alarms, this function
provides an even more conspicuous indication that
an alarm condition has occurred.

When enabled, the function alternates the indicator
display between the numerical value and the alarm
reference, ‘ALr1’ or ‘ALr2’, when the alarm output
is activated.  If both alarm outputs are activated,
the alarm references are displayed in sequence.

To enable or disable the function select 'FLSH'
from the alarm menu and press 

P

 which will reveal

the current setting ‘on’ or ‘oFF’.  The function can
changed by pressing the 

 or 

 button followed

by the 

E

 button to return to the alarm menu.

8.3.11 Access setpoint in display mode:  ACSP

This function enables a separate menu providing
access to the alarm setpoints from the display
mode by simultaneously operating the 

P

 and 

push-buttons.  An operator can therefore adjust the
alarm setpoints without having access to the
indicator configuration menu.  Protection against
accidental adjustment of the setpoints when the

indicator is in the display mode is provided by a
separate security code.

This direct setpoint access menu is enabled and
the separate security code entered from the
'ACSP' function in the alarm configuration menu as
shown in Fig 12.  To change the menu parameters
select 'ACSP' from the configuration menu and
press 

P

 

which will display the enable prompt

'EnbL'.  Press 

P

 again to reveal if the direct access

menu is 'on' or 'oFF'.  The 

 or 

 button will

toggle the display between the two conditions.

If 'oFF' is selected, the operator will not have
access to the setpoints from the display mode.
Return to the 'ACSP' prompt in the main menu by
pressing

 

E

 twice.

If 'on' is selected, the operator will have direct
access to the alarm setpoints from the display
mode via a separate optional security code.   To
define this four digit security code press 

P

 to return

to the 'Enbl' prompt followed by the 

 or 

 button

to select the access code prompt 'ACCd'.
Pressing 

P

 

will reveal the current security code.

Each digit of the code may be changed by
operating the 

 and 

 push-buttons, and the 

P

button to move control to the next digit.  When the
required code has been entered, press 

E

 twice to

return to the 'ACSP' prompt in the configuration
menu.

Default code 0000 will disable the security code
allowing direct access to the setpoints in the
display mode by pressing the

 

P

 

and 

 buttons

simultaneously.  Unless otherwise requested new
instruments with alarms are supplied with this
function disabled and the security code set to
0000.

8.3.12  Adjusting alarm setpoints from the
            display mode

Access to the alarm setpoints from the indicator
display mode is obtained by operating the 

P

 and 

push-buttons simultaneously as shown in Fig 13.
If the setpoints are not protected by a security
code the alarm setpoint prompt 'SP1' will be
displayed.  If the setpoints are protected by a
security code, 'Code' will be displayed first.
Pressing 

P

 again will enable the alarm security

code to be entered digit by digit using the 

 and

 buttons to change the flashing digit, and the 

P

push-button to move control to the next digit.  If the
correct code is entered pressing 

E

 

will cause alarm

setpoint prompt 'SP1' to be displayed.  Pressing
the 

 or 

 button will toggle the display between

the two alarm setpoint prompts 'SP1' and 'SP2'.

If an incorrect security code is entered, or a button
is not pressed within twenty seconds, the indicator
will automatically return to the display mode.

Summary of Contents for BA504E

Page 1: ...Issue 2 14th December 2011 BA504E BA524E General Purpose loop powered field mounting indicators Issue 2...

Page 2: ...ver range 6 5 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Custom...

Page 3: ...e g temperature flow pressure or level The BA504E and BA524E are not certified for use in explosive atmospheres For hazardous area application the BA304E BA304NE BA324E or the BA324NE should be used 2...

Page 4: ...indicator and the ACSP access setpoints in display mode function has been enabled P E Provides access to the configuration menu via optional security code Note BA524E only If the indicator has been c...

Page 5: ...ally joined and may be used for linking cable screens The indicator s earth terminal is connected to the carbon loaded GRP enclosure If this enclosure is not bolted to an earthed post or structure the...

Page 6: ...EMC Both instruments compy with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs with the screens connected at one poin...

Page 7: ...tion Default Configuration BA504E BA524E Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph...

Page 8: ...8...

Page 9: ...n 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or pre...

Page 10: ...etween the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the...

Page 11: ...n and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit secur...

Page 12: ...r volumetric units by filling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break point required should f...

Page 13: ...13...

Page 14: ...dd a break point Adds a new break point before the displayed break point The calibration of existing break points is not changed but the identification number of all subsequent break point is increase...

Page 15: ...tor display at the first break point When set as required press E to return to the 0 n prompt from which the the next break point can be selected using the or buttons When the required break point has...

Page 16: ...If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop w...

Page 17: ...n Both indicators can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9...

Page 18: ...polarised and current will only flow in one direction Ron less than 5 0 7V Roff greater than 1M Fig 10 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switc...

Page 19: ...19...

Page 20: ...setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function as High or Low See section 8 3 5 no nC Normally open or...

Page 21: ...r fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 22: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 23: ...int plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 14 Fig 14 Displayed value and setpoints on bargra...

Page 24: ...cting it in series with the indicator s 4 20mA input as shown in Fig 16 which increases the maximum indicator voltage drop from 1 2 to 5V Fig 16 Loop powered backlight Providing the increased voltage...

Page 25: ...l pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel b...

Reviews: