The indicator’s digital display at which the
bargraph starts is defined by the ‘bArLo’ sub-
function which is selected by pressing the 

button followed by the 

P

 button which will reveal

the current indicator display at which the bargraph
starts.   The flashing digit can be adjusted by
pressing the 

 or 

 buttons, when set as required

pressing 

P

 

will transfer control to the next digit.

When all the digits have been adjusted, press 

E

 to

return to the 'bArLo' prompt from which ‘bArHi’
which defines the finishing point of the bargraph
can be selected by pressing the 

 button.   ‘bArHi’

is adjusted in the same way as ‘bArLo’.   When set
as required, pressing 

E

 twice will return the display

to the ‘bAr’ prompt in the configuration menu.

Note:

  ‘bArLo’ must be set lower than ‘bArHi’,

incorrect setting is indicated by the bargraph scale
flashing with a single bargraph segment activated.

5.8  Function of the 

P

 push-button:   ‘C - - P’

When the indicator is in the display mode,
operating the 

P

 push-button will display the input

current in milliamps, or the displayed value as a
percentage of the difference between the
displayed values at 4mA and 20mA inputs.

To check or change the function of the 

P

 push-

button select 'C - -P' from the configuration menu
and press 

P

 to reveal the current setting.  Pressing

the 

 or 

 button will toggle the setting between

'4-20' the current display in milliamps and 'PC' the
percentage display.   When set as required press

E

 to return to the ‘C - - P’ prompt in the

configuration menu.

5.9  Tare function:   ‘tArE’

The tare function is primarily intended for use with
weighing system.  When the indicator is in the
display mode and the tare function is activated,
pressing the 

E

 button for more than three seconds

will zero the indicator’s digital display and activate
the tare annunciator.  On the BA524E the bargraph
remains linked to the digital display when the tare
function is activated.   Subsequent operation of the

E

 push-button for less than 3 seconds will return

the indicator to the gross display and deactivate
the tare annunciator.

To check or change the tare function select 'tARE'
from the configuration menu and press 

P

 to reveal

the current setting.  Pressing the 

 or 

 button

will toggle the setting between 'on' and 'oFF'.
When set as required press 

E

 to return to the

‘tARE’ prompt in the configuration menu.

5.10  Security code:  ‘CodE’

Access to the instrument configuration menu may
be protected by a four digit security code which

must be entered to gain access.   New instruments
are configured with the default security code 0000
which allows unrestricted access to all
configuration functions.

To enter a new security code select 'CodE' from
the configuration menu and press

 

P

 which will

cause the indicator to display the existing security
code with one digit flashing.  The flashing digit can
be adjusted using the 

 and

 

 push-buttons,

when set as required operating the 

P

 button will

transfer control to the next digit.   When all the
digits have been adjusted press

 

E

 to return to the

‘CodE’ prompt in the configuration menu. The
revised security code will be activated when the
indicator is returned to the display mode.  Please
contact BEKA associates sales department if the
security code is lost.

5.11  Reset to factory defaults:  ‘rSEt’

This function enables the indicator and the
lineariser to be quickly returned to the factory
default configurations shown in sections 5.0 and
6.5

To reset the indicator or lineariser select ‘rSEt’
from the configuration menu and press 

P

, the

indicator will display one of the reset options
‘ConF’ or ‘LtAb’.

‘ConF’

Resets the indicator to defaults

‘LtAb’

Resets the lineariser to defaults

Using the 

 or 

 push-button select the required

sub-function and press 

P.

  To prevent accidental

resetting the request must be confirmed by
entering ‘5urE’.   Using the 

 button set the first

flashing digit to ‘5’ and press 

P

 to transfer control

to the second digit which should be set to ‘u’.
When ‘5urE’ has been entered pressing the 

E

button will reset the selected configuration menus
and return the display to the ‘rSEt’ function in the
configuration menu.

5.12  Under and over-range

If the numerical display range of the indicator is
exceeded, all the decimal points will flash as
shown below:

BA504E

 BA524E

  Underrange

-9.9.9.9

-9.9.9.9.9

  Overrange

 9.9.9.9

 9.9.9.9.9

Although not guaranteed, most indicators will
continue to function normally with an input current
between 1.8mA and 4mA, at lower currents the
instrument will display ‘LPLo’ before it stops
functioning.
Under or overrange of the BA524E bargraph is
indicated by an activated arrow at the appropriate
end of the bargraph and a flashing bargraph scale.

Summary of Contents for BA504E

Page 1: ...Issue 2 14th December 2011 BA504E BA524E General Purpose loop powered field mounting indicators Issue 2...

Page 2: ...ver range 6 5 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Custom...

Page 3: ...e g temperature flow pressure or level The BA504E and BA524E are not certified for use in explosive atmospheres For hazardous area application the BA304E BA304NE BA324E or the BA324NE should be used 2...

Page 4: ...indicator and the ACSP access setpoints in display mode function has been enabled P E Provides access to the configuration menu via optional security code Note BA524E only If the indicator has been c...

Page 5: ...ally joined and may be used for linking cable screens The indicator s earth terminal is connected to the carbon loaded GRP enclosure If this enclosure is not bolted to an earthed post or structure the...

Page 6: ...EMC Both instruments compy with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs with the screens connected at one poin...

Page 7: ...tion Default Configuration BA504E BA524E Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph...

Page 8: ...8...

Page 9: ...n 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or pre...

Page 10: ...etween the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the...

Page 11: ...n and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit secur...

Page 12: ...r volumetric units by filling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break point required should f...

Page 13: ...13...

Page 14: ...dd a break point Adds a new break point before the displayed break point The calibration of existing break points is not changed but the identification number of all subsequent break point is increase...

Page 15: ...tor display at the first break point When set as required press E to return to the 0 n prompt from which the the next break point can be selected using the or buttons When the required break point has...

Page 16: ...If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop w...

Page 17: ...n Both indicators can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9...

Page 18: ...polarised and current will only flow in one direction Ron less than 5 0 7V Roff greater than 1M Fig 10 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switc...

Page 19: ...19...

Page 20: ...setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function as High or Low See section 8 3 5 no nC Normally open or...

Page 21: ...r fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 22: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 23: ...int plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 14 Fig 14 Displayed value and setpoints on bargra...

Page 24: ...cting it in series with the indicator s 4 20mA input as shown in Fig 16 which increases the maximum indicator voltage drop from 1 2 to 5V Fig 16 Loop powered backlight Providing the increased voltage...

Page 25: ...l pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel b...

Reviews: